NOMINAL CAPACITY, CAPACITY STEPS and NOMINAL INPUT
UNITS EUWL16KZW EUWL20KZW EUWL24KZW
NOMINAL CAPACITY (1) Cooling kW 40.0 53.7 62.4
CAPACITY STEPS % 2 2 2
NOMINAL INPUT (2) ** Cooling kW 13.5 18.0 20.5
EER 2.96 2.98 3.04
TECHNICAL SPECIFICATIONS
UNITS EUWL16KZW EUWL20KZW EUWL24KZW
DIMENSIONS Unit H mm 600
W mm 600
D mm 1,200
WEIGHT Machine weight kg 252 265 274
MATERIAL Polyester painted steel plate
COLOUR Ivory white / Munsell code 5Y7.5/1
SOUND LEVEL Sound pressure dBA −−−
Sound power dBA 67 67 74
WATER HEAT EXCHANGER Type Brased plate heat exchanger
Qty 1 1 1
Minimum water volume in the system l 205 268 311
Nominal water flow l/min 115 154 179
Water flow range (min/max) l/min 57/229 77/307 89/358
Insulation material Polyethylene foam
REFRIGERANT CIRCUIT Refrigerant type R-407C
Refrigerant charge kg N2 holding charge
Refrigerant charge formula (***) See 8hp x 2 See 10hp x 2 See 12hp x 2
No. of circuits 2 2 2
Refrigerant control Thermostatic expansion valve
COMPRESSOR Type x qty Hermetically sealed scroll
No. of compressors 2 2 2
Model JT212DA-YE JT300DA-YE JT335DA-YE
Speed rpm 2,900 2,900 2,900
Refrigerant oil type FVC68D
Refrigerant oil charge l 2 x 2.7 2 x 2.7 2 x 2.7
Crankcase heater W 2 x 33
PIPING CONNECTIONS Evap. water in/outlet mm FBSP 40
Evaporator drain / purge Field installation
Discharge connection mm 2 x 19.1 flare 2 x 19.1 flare 2 x 19.1 flare
Liquid connection mm 2 x 12.7 flare 2 x 12.7 flare 2 x 12.7 flare
Filter strainer Field installation
Flow switch Field installation
Max. length / circuit (****) m 50
Max. height/ circuit (****) m 30
SAFETY DEVICES High pressure switch / Low pressure switch / Freeze-up protection / Reverse phase protector / Discharge temperature protection /
Compressor motor overcurrent / Anti recycling timer / Guard timer / Liquid line solenoid valve / Suction accumulator / Crankcase
heater