Daikin EUWL12KZW [9/21] Specifications

Daikin EUWL12KZW [9/21] Specifications
ELECTRICAL SPECIFICATIONS
UNITS EUWL5KZW EUWL8KZW EUWL10KZW EUWL12KZW
POWER SUPPLY W1 W1 W1 W1
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 3N 3N 3N 3N
Frequency Hz 50 50 50 50
Voltage V 400 400 400 400
Voltage tolerance % ± 10 ± 10 ± 10 ± 10
UNIT Starting current A 49 79 109 129
Nominal running current A 7.4 11.6 14.7 16.8
Maximum running current A 8 14 18 20
Recommended fuses according to IEC
standard 269-2
aM 3x16 3x20 3x25 3x25
COMPRESSOR Phase 3 3 3 3
Voltage V 400 400 400 400
Starting current A 49 79 109 129
Nominal running current A 7.4 11.6 14.7 16.8
Maximum running current A 8 14 18 20
Starting method Direct on line
ELECTRICAL SPECIFICATIONS
UNITS EUWL16KZW EUWL20KZW EUWL24KZW
POWER SUPPLY W1 W1 W1
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 3N 3N 3N
Frequency Hz 50 50 50
Voltage V 400 400 400
Voltage tolerance % ± 10 ± 10 ± 10
UNIT Starting current A 93 127 149
Nominal running current A 23.2 29.5 33.6
Maximum running current A 28 36 40
Recommended fuses according to IEC
standard 269-2
aM 3x35 3x40 3x50
COMPRESSOR Phase 3 3 3
Voltage V 400 400 400
Starting current A 79 109 129
Nominal running current A 11.6 14.7 16.8
Maximum running current A 14 18 20
Starting method Direct on line
NOTES
1 Nominal cooling capacity at Eurovent conditions:
See Eurovent 6/C/003
Entering / leaving water temperature = 12°C/7°C - condensing temperature = 45°C(*) - liquid temperature = 40°C
2 Nominal power input at Eurovent conditions:
See Eurovent 6/C/003
Entering / leaving water temperature = 12°C/7°C - condensing temperature = 45°C(*) - liquid temperature = 40°C
3 Waterflow rate (WFR) = (860xCC) / (60xDt) in (l/min)
4 No pumps are supplied with the unit, so the added power input for the pumps is calculated as (WFR m
3
/s x DPa) m
3
/s /0.3 as fixed by 6/C/003
(Dp = pressure drop from pressure drop curves).
A filter strainer must be added in the water circuit of the evaporator (field installation). A flow switch must be provided at the evaporator
side. Min. water volume applicable at nominal conditions.
5 For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’ and select
’’conditional connection’’,
Finally, click on the document title of your choice.
(*)This temperature corresponds to compressor discharge pressure
(**) Includes besides the power input of the unit also an addition for the required evaporator pump power input
(***) VRC = Volume remote condenser; LLP = Length liquid piping
(****) Length = total length of liquid line or discharge line
Height = height difference between unit and remote condenser
Remote condenser R-407C EUWL5-24KZW
3
Specifications
1
3
7
Applied Systems Chillers