Variable Primary Flow(opt. code 143)
By selecting opt. 143 the chiller can manage the Variable Primary water flow according to the differential
pressuremeasured in aspecific pointof the plant,selected bythe plant designer). Thedifferential pressure
transducer,isavailableasoptionfromthefactrory(opt.code144).Onceplacedontheplantthedifferential
pressuretransducermustbeconnectedtotheunit.Asalternativetheunitcontrollercanreceivedirectlythe
differentialpressurevaluefromanexternalBMScommunicatingwiththestandardscommunicationsprotocols
(eg.MODBUS).
Abypassline(fieldsupply)needstobeinstalledwhichguaranteesthatatalltimestheminimumwaterflowof
thechillerissupplied(refertothe“Operatinglimit”chapterforindicationonminimumwaterflow).Thebypass
valve will be an ON/OFF normally closed valve controlled by the chiller. In case the minimum water flow
allowedisnotreached,thechillerwillopenthebypasslinerestoringthewaterflowabovetheminimumvalue.
Incaseofmultipleunitsinstallationsinaprimaryonlyplantoperatingwithvariableflowcontactfactory.