Daikin EWAD360TZ-SLB1 [41/104] Electrical specifications

Daikin EWAD360TZ-SLB1 [41/104] Electrical specifications
EWAD~TZ-SS B
INV
INV
INV
INV
INV
INV
Startingmethod
218
204
171
162
150
139
A
Maximumrunningcurrent
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
3
3
3
3
3
3
No.
Phases
COMPRESSORS
31.2
31.2
31.2
26
20.8
20.8
A
Nominalrunningcurrentcooling
FANS
483
479
374
368
349
313
A
Maximumcurrentforwiressizing
466
439
374
350
320
298
A
Maximumrunningcurrent
396
377
361
366
372
246
A
Nominalrunningcurrentcooling
335
315
268
254
230
214
A
Maximumstartingcurrent
UNIT
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
50
50
50
50
50
50
Hz
Frequency
3
3
3
3
3
3
No.
Phases
POWER SUPPLY
EWAD660TZ
-SS B2
EWAD610TZ
-SS B2
EWAD570TZ
-SS B2
EWAD495TZ
-SS B2
EWAD450TZ
-SS B2
EWAD380TZ
-SS B2
MODEL
INV
INV
INV
INV
INV
INV
Startingmethod
225
204
171
150
139
119
A
Maximumrunningcurrent
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
3
3
3
3
3
3
No.
Phases
COMPRESSORS
20.8
15.6
15.6
10.4
10.4
10.4
A
Nominalrunningcurrentcooling
FANS
247
239
187
174
156
141
A
Maximumcurrentforwiressizing
246
220
187
160
149
130
A
Maximumrunningcurrent
200
188
177
188
123
102
A
Nominalrunningcurrentcooling
151
137
115
100
93
80
A
Maximumstartingcurrent
UNIT
10%
10%
10%
10%
10%
10%
%
VoltagetoleranceMaximum
-10%
-10%
-10%
-10%
-10%
-10%
%
VoltagetoleranceMinimum
400
400
400
400
400
400
V
Voltage
50
50
50
50
50
50
Hz
Frequency
3
3
3
3
3
3
No.
Phases
POWER SUPPLY
EWAD360TZ
-SS B1
EWAD300TZ
-SS B1
EWAD270TZ
-SS B1
EWAD240TZ
-SS B1
EWAD190TZ
-SS B1
EWAD160TZ
-SS B1
MODEL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Plese refer to unit nameplate data.
41/104
ELECTRICAL SPECIFICATIONS