Daikin EWAD360TZ-SLB1 [16/104] Options

Daikin EWAD610TZ-SLB2 [16/104] Options
Rapid restart (opt. code 110)
RapidRestartis theidealsolution for those applicationwherewe cannotafford thelooseof cooling such as
data centers, health care facilities, process cooling …etc. For this kind of applications, in case of a power
failure,chillerequipmentarerequiredtorestorethecoolingsupplytothesystemasfastaspossible.Standard
unit(withouttheRapidRestartoption)willbestartingwithin310secondsafterthepoweris restoredandit
willbereachingfullloadcoolingcapacitywithin20÷25minutes(obviouslydependingontheloaddemand).
RapidRestartisallowingthechillertostartasfastas30secondsafterpowerisrestoredandtoreachfullload
coolingcapacityinlessthan6minutesfromtheunitrestart.
FormoredetailsaboutthisoptionpleaserefertotheControlManual.

Compressors circuit breakers (opt. code 95)
Safety devices that include in a single device all safety functions otherwise provided by standard fuses and
optionalthermalrelays,suchasprotectionagainstovercurrent,overload,currentunbalance.

Fans circuit breakers (opt. code 96- provided as standard)
Safety devices that, added to the standard protection devices, protect fan motors against overload and
overcurrent.

Fans speed regulation (INVERTER) (opt. code 99a provided as standard on GOLD series)
AvailableonSilverseriesasoption.
NotavailableonPlatinumseriesthatprovidestheECfansasstandard.

EC motor fans (opt. code 145 - provided as standard on PLATINUM series)
AvailableonSilverandGOLDseriesasoption

High ambient kit (opt. code 146)
Thehighambientkitallowstheoperationoftheunitforambienttemperatureabove46°C.
ThesetupoftheunitswithHighambientkitarethefollows:
·SILVERseries:oversizedelectricalequipment,enhancedventilationfortheelectricalbox,sunshield,6poles
ACfans(fansspeed900RPM)
Note:theperformancewilldifferfromthestandardunit.Contactfactoryforinformation.
·GOLD series:oversizedelectricalequipment,enhancedventilationfortheelectricalbox,sunshield,ECfans
(fansspeedupto900RPM).
·PLATINUM series:oversizedelectricalequipment,enhancedventilationfortheelectricalbox,sunshield,EC
fans(fansspeedupto900RPM)
Note:Opt.146isnotcompatiblewithopt.08Brine

Set point reset, demand limit and alarm from external device (opt. code 90provided as standard)
SetpointReset:Theleavingwatertemperatureset-pointcanbeoverwrittenwithanexternal4-20mA,through
the ambient temperature, or through the evaporator water temperature ΔT. Demand Limit: Chiller capacity
can be limited through an external 4-20mA signal or via network. Alarm from external device: The unit
controllerisabletoreceiveanexternalalarmsignal.Theusercandecidewhetherthisalarmsignalwillstop
theunitornot.

Rubber anti vibration mounts (opt. code 75)
Supplied separately, these are positioned under the base of the unit during installation. Ideal to reduce the
vibrationswhentheunitisfloormounted.

Spring anti vibration mounts (opt. code 77)
Suppliedseparately,thesearepositionedunderthe base oftheunitduringinstallation.Idealfordampening
vibrationsforinstallationonroofsandmetallicstructures.

Container Kit (opt. code 71)
Transport kit (opt. code 112)
16/104
OPTIONS

Содержание

Скачать