Daikin EWAH170TZ-SLB1 [58/102] Ewah tz srb

Daikin EWAH220TZ-XSB1 [58/102] Ewah tz srb
57/100
SOUND LEVELS
EWAH~TZ-SRB
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Power db
(A)
MODEL
63 Hz
250 Hz
500 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
170
69.5
65.5
68.5
58.5
51.5
43.5
69
88
200
69.8
65.8
68.8
58.8
51.8
43.8
69
88
240
71.6
67.6
70.6
60.6
53.6
45.6
71
90
290
72.9
69.9
72.9
62.9
54.9
47.9
73
92
330
72.9
69.9
72.9
62.9
54.9
47.9
73
92
390
70.9
67.9
70.9
60.9
52.9
45.9
71
91
420
71.1
68.1
71.1
61.1
53.1
46.1
71
92
490
72.3
69.3
72.3
62.3
54.3
47.3
72
93
530
74.0
71.0
74.0
64.0
56.0
49.0
74
95
600
74.6
71.6
74.6
64.6
56.6
49.6
75
95
690
74.5
71.5
74.5
64.5
56.5
49.5
74
95
750
74.3
71.3
74.3
64.3
56.3
49.3
74
96
820
57.1
65.9
73.6
65.2
57.1
49.7
73
95
920
57.9
66.7
74.4
66.0
57.9
50.5
74
96
980
58.2
67.0
74.7
66.3
58.2
50.8
74
97
C10
58.7
67.5
75.2
66.8
58.7
51.3
75
97
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.
The data are referred to the standard unit without options.