58/100
SOUND LEVELS
EWAH~TZ-XSB
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Power db
(A)
MODEL
63 Hz
250 Hz
500 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
180
78.5
74.5
77.5
67.5
60.5
52.5
78
97
220
79.0
75.0
78.0
68.0
61.0
53.0
78
98
270
81.8
78.8
81.8
71.8
63.8
56.8
82
101
300
81.4
78.4
81.4
71.4
63.4
56.4
81
101
350
79.3
76.3
79.3
69.3
61.3
54.3
79
100
390
79.5
76.5
79.5
69.5
61.5
54.5
80
100
430
79.4
76.4
79.4
69.4
61.4
54.4
80
101
480
80.3
77.3
80.3
70.3
62.3
55.3
80
102
580
83.5
80.5
83.5
73.5
65.5
58.5
83
104
620
82.9
79.9
82.9
72.9
64.9
57.9
83
104
670
82.9
79.9
82.9
72.9
64.9
57.9
83
104
710
82.6
79.6
82.6
72.6
64.6
57.6
82
104
760
82.3
79.3
82.3
72.3
64.3
57.3
82
104
820
66.0
74.8
82.5
74.1
66.0
58.6
82
104
930
66.9
75.7
83.4
75.0
66.9
59.5
83
106
990
67.6
76.4
84.1
75.7
67.6
60.2
84
106
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.
The data are referred to the standard unit without options.