Daikin EWAD420T-XSB2 [38/81] Frequency

Daikin EWADC19T-XSB3 [38/81] Frequency
32/73
ELECTRICAL SPECIFICATIONS
EWAD~T-SSB
MODEL
EWADH10T-
SS B2
EWADC11T-
SS B2
EWADH12T-
SS B2
EWADH13T-
SS B2
EWADH15T-
SS B3
POWER SUPPLY
Phases
No.
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
773
797
877
925
1075
Nominal running current cooling
A
572.46
610
692.46
727.9
839
Maximum running current
A
709
768
838
897
986
Maximum current for wires sizing
A
776
840
918
982
1079
FANS
Nominal running current cooling
A
36.12
41.28
41.28
46.44
56.8
COMPRESSORS
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
Maximum running current
A
398
452
398
452
310
Starting method
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
MODEL
EWADH16T-
SS B3
EWADC17T-
SS B3
EWADH18T-
SS B3
EWADC19T-
SS B3
EWADC21T-
SS B3
POWER SUPPLY
Phases
No.
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
1161
1217
1217
1270
1324
Nominal running current cooling
A
885
951
1029
1073
1158
Maximum running current
A
1118
1188
1257
1323
1455
Maximum current for wires sizing
A
1223
1300
1377
1449
1592
FANS
Nominal running current cooling
A
61.9
61.9
61.9
67.08
77.4
COMPRESSORS
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
Maximum running current
A
398
398
398
459
459
Starting method
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.