Daikin EWAD730T-XLB2 [37/81] Ewad800t

Daikin EWADC10T-SSB2 [37/81] Fans nominal running current cooling
31/73
ELECTRICAL SPECIFICATIONS
EWAD~T-SSB
MODEL
EWAD290T-
SS B2
EWAD330T-
SS B2
EWAD370T-
SS B2
EWAD400T-
SS B2
EWAD430T-
SS B2
POWER SUPPLY
Phases
No.
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
253
264
306
399
417
Nominal running current cooling
A
76.76
94.25
195.63
109.02
123.85
Maximum running current
A
211
242
272
294
316
Maximum current for wires sizing
A
231
265
297
322
346
FANS
Nominal running current cooling
A
15.48
15.48
20.64
20.64
20.64
COMPRESSORS
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
Maximum running current
A
82
99
126
126
148
Starting method
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
MODEL
EWAD520T-
SS B2
EWAD580T-
SS B2
EWAD700T-
SS B2
EWAD800T-
SS B2
EWAD940T-
SS B2
POWER SUPPLY
Phases
No.
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
493
493
574
645
697
Nominal running current cooling
A
148.11
171.97
370.76
422.34
486.54
Maximum running current
A
373
395
492
536
621
Maximum current for wires sizing
A
408
432
538
587
679
FANS
Nominal running current cooling
A
25.8
25.8
30.96
30.96
36.12
COMPRESSORS
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
Maximum running current
A
162
185
274
274
398
Starting method
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.