Daikin EWAD730T-XLB2 [47/81] Compressors

Daikin EWADC17T-XRB3 [47/81] Compressors
41/73
ELECTRICAL SPECIFICATIONS
EWAD~T-XLB
MODEL
EWAD730T-
XR B2
EWAD820T-
XR B2
EWAD950T-
XR B2
EWADC10T-
XR B2
EWADH10T-
XR B2
POWER SUPPLY
Phases
No.
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
567
638
696
701
769
Nominal running current cooling
A
379.04
433.58
477.39
533.75
552.3
Maximum running current
A
478
523
608
662
699
Maximum current for wires sizing
A
524
573
666
725
766
FANS
Nominal running current cooling
A
17.28
17.28
23.04
23.04
25.9
COMPRESSORS
Phases
No.
3
3
3
3
3
Voltage
V
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
Maximum running current
A
274
274
398
452
398
Starting method
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
MODEL
EWADC13T-
XR B2
EWADH13T-
XR B2
EWADC14T-
XR B2
EWADH15T-
XR B3
EWADH16T-
XR B3
EWADC17T-
XR B3
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
871
917
925
1057
1146
1204
Nominal running current cooling
A
675.01
711.6
769.5
834
883
941
Maximum running current
A
826
882
936
964
1093
1166
Maximum current for wires sizing
A
905
967
1026
1057
1199
1279
FANS
Nominal running current cooling
A
28.8
31.7
31.68
34.6
37.4
40.3
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum %
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum %
10%
10%
10%
10%
10%
10%
Maximum running current
A
398
452
452
310
398
398
Starting method
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Y-Δ
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load.
In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.