Daikin EWWH490DZXEA2 [16/47] Rapid restart

Daikin EWWHC14DZXEA3 [16/47] Rapid restart
D-EOMWC01405-18EN
16/47
EWWD_DZ EWWH_DZ
Standby Reset=
Off
Off, Reset
Parameter to reset standby chiller cycling timer
4.2.6 Rapid Restart
This page shows if the function Rapid Restart is enabled by external contact and it allows to define the maximum black out
time in order to recover quickly the unit load.
Setpoint/Sub-Menu
Range
Description
Rapid Restart=
Enable, Disable
Feature enable if Rapid Restart is installed
Pwr Off Time=
-
Maximum black out time to enable Rapid Restart
4.2.7 Date/Time
This page will allow to adjust the time and date in the UC. This time and date will be used in the alarm log and to enable
and disable the Quiet Mode. Additionally it’s also possible to set the starting and ending date for the DayLight Saving time
(DLS) if used. Quiet Mode is a feature that is used to reduce the chiller noise. This is done by applying the maximum
setpoint reset to the cooling setpoint and increasing the condenser temperature target by an adjustable offset.
Setpoint/Sub-Menu
Default
Range
Description
Actual Time=
12:00:00
Set the time
Actual Date=
01/01/2014
Set the date
UTC Diff=
-60min
Difference with UTC
DLS Enable=
Yes
No, Yes
Enable DayLight Saving time
DLS Strt Month=
Mar
DayLight Saving time start month
DLS Strt Week=
2ndWeek
DayLight Saving time start week
DLS End Month=
Nov
NA, Jan…Dec
DayLight Saving time end month
DLS End Week=
1stWeek
1
st
…5
th
week
DayLight Saving time end week
On board real time clock settings are maintained thanks to a battery mounted on the controller. Make sure that the battery
is replaced regularly each 2 years (see section 3.5).
4.2.8 Scheduler
This page allows to program the time scheduler
Setpoint/Sub-Menu
Default
Range
Description
State
Off
Off, On Setpoint 1, On Setpoint 2
Actual state provided by the time scheduler
Monday
-
Link to Monday scheduler programming page
Tuesday
-
Link to Tuesday scheduler programming page
Wednesday
-
Link to Wednesday scheduler programming page
Thursday
-
Link to Thursday scheduler programming page
Friday
-
Link to Friday scheduler programming page
Saturday
-
Link to Saturday scheduler programming page
Sunday
-
Link to Sunday scheduler programming page
Table below reports the menu used to program daily time slots. Six time slots can be programmed by the user.
Setpoint/Sub-Menu
Default
Range
Description
Time 1
*:*
0:00..23:59
Define the starting time of 1
st
time slot
Value 1
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 1
st
time slot
Time 2
*:*
0:00..23:59
Define the starting time of 2
nd
time slot
Value 2
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 2
nd
time slot
Time 3
*:*
0:00..23:59
Define the starting time of 3
rd
time slot
Value 3
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 3
rd
time slot
Time 4
*:*
0:00..23:59
Define the starting time of 4
th
time slot
Value 4
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 4
th
time slot
Time 5
*:*
0:00..23:59
Define the starting time of 5
th
time slot
Value 5
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 5
th
time slot
Time 6
*:*
0:00..23:59
Define the starting time of 6
th
time slot
Value 6
Off
Off, On Setpoint 1, On Setpoint 2
Define the unit state during 6
th
time slot
4.2.9 Power Conservation
This page resumes all the settings that allows chiller capacity limitations. Further explanations of the setpoint reset options
can be found in the chapter 7.1.
Setpoint/Sub-
Menu
Default
Range
Description
Unit Capacity=
100.0%
Demand Lim En=
Disable
Disable, Enable
Demand Limit Enable
Demand Limit=
100.0%
Demand Limit Mode - Active demand limitation