6.6.6 Evaporating Pressure sensor fault
This alarm indicates that the evaporating pressure transducer is not operating properly.
Symptom
Cause
Solution
Circuit status is Off.
The circuit is stopped.
Bell icon is moving on controller’s display.
String in the alarm list:
CxCmp1 EvapPressSen
String in the alarm log:
CxCmp1 EvapPressSen
String in the alarm snapshot
CxCmp1 EvapPressSen
Sensor is broken.
Check for sensor integrity.
Check correct sensors operation
according information about mVolt (mV)
range related to pressure values in kPa.
Sensor is shorted.
Check if sensor is shorted with a
resistance measurement.
Sensor is not properly connected (open).
Check for correct installation of the sensor
on refrigerant circuit pipe. The transducer
must be able to sense the pressure
through the valve’s needle.
Check for absence of water or humidity on
sensor electrical contacts.
Check for correct plug-in of the electrical
connectors.
Check for correct sensors wiring also
according electrical scheme.
Reset
Notes
Local HMI
Network
Auto
6.6.7 EXV Driver Error
This alarm indicates an abnormal condition of the EXV Driver.
Cause
Solution
Circuit status is Off.
Hardware Error
Contact your service organization to get
the problem solved.
Notes
Local HMI
6.6.8 High Discharge Temperature Alarm
This alarm indicates that the temperature at the discharge port of the compressor exceeded a maximum limit which may
cause damages to the mechanical parts of the compressor.
When this alarm occurs compressor’s crankcase and discharge pipes may become very hot. Be careful
when getting in contact with the compressor and discharge pipes in this condition.
Symptom
Cause
Solution
Circuit status is Off.
The compressor does not load anymore or
even unload, circuit is stopped.
Liquid Injection solenoid valve is not
operating properly.
Check the electrical connection between
the controller and the liquid injection
solenoid valve.