MEAN WELL RCP-2000-48 [5/5] Rcp 2000

MEAN WELL RCP-2000-48 [5/5] Rcp 2000
File N ame:RCP- 2 000-SPEC 2013-11-01
2000W Front End Power Supply
R CP-200 0
s eries
(1)Output voltage can be trimmed between 90~110% of its rated value by the following method.
(2)+S & +V, -S & -V also need to be connected on CN501.
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
+V
-V
+S
-S
RCP-2 000
14
15
3. Output Voltage Trimming
PV
-S
-V
+V
+S
RCP- 2000
11
15
14
0~5V
-V Signal
Add on 0~5V external voltage
9
60
70
80
EXTERNAL VOLTAGE (DC)
90
100
110
Vout
0.50 1.5 3 4.5 5
V
Function
AC-OK
AC-NG
DC-OK
DC-NG
T-OK
T-ALARM
LED
GREEN
RED
GREEN
RED
GREEN
RED
Description
When input voltage 87V
When input voltage 75V
When output voltage 80% 5% of Vo rated. ±
When output voltage 80% 5% of Vo rated. ±
When the internal temperature (TSW1 & TSW2 short) is within safe limit
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
4. Front Panel Indicators & Corresponding Signal at Function Pins
Signal
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
4.5 ~ 5.5V
PSU Output
ON
OFF
ON
ON
ON
OFF
*
*Signal between function pin and "GND-AUX".
LOAD