Daikin EWAQ021BAWP [174/223] Troubleshooting

Daikin EWYQ016BAWN [174/223] Troubleshooting
ESIE11-05 Error Codes
Troubleshooting 163
4.42 U4
Troubleshooting
Rectify.
Replace PCB A1P.
Is error U4
still showing?
Bad
connection?
Communication problem was solved.
Check wiring of D3 net
F1/F2 communicates
Check A1P X30[3,4] outdoor unit.
Reset the power supply.
YES
YES
NO
NO