ESIE11-05 Special Control
Functional Description 49
3.4 Standby
3.4.1 Restart Standby
Used to forcedly stop the compressor for a period of 3 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
* Actuators are based on EWYQ032BA.
3.4.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this
mode is used to control the crankcase heater.
Actuator Operation
Compressor OFF
Outdoor unit fan
Ta>30°C: STEP4
Ta30°C: OFF
Four way valve Holds
Main electronic expansion valve (EV1) 0 pls
Subcooling electronic expansion valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
Hydrobox electronic expansion valve (K11E) 0 pls
Hydrobox electronic expansion valve (K21E) 0 pls
Accumulator oil return valve (SVO) OFF
Ending conditions 3 min.
Crankcase heater
OFF
Crankcase heater
ON
Discharge pipe
temperature < 70
°C
Discharge pipe
temperature > 75
°C