Daikin EWAQ021BAWP [197/223] Options

Daikin EWAQ032BAWN [197/223] Options
Options ESIE11-05
186 Service Procedure
5. Options
5.1 EKRP1AHT
5.1.1 General
This option is for:
Remote ON/OFF
Switching between cooling/heating (field settings needed)
Thermostat ON/OFF (field settings needed)
The PCB is placed in the hydrobox. The switch box connects X80A (A4P or A6P) with X85A
(A1P or A5P).
Quantity:
1 PCB is needed for EW*Q016BA-032BA
2 PCBs are needed for EW*Q040BA-064BA
Connection:
1-5: depending on field setting
2-5: depending on field setting
3-5: operation ON
4-5: operation OFF