Daikin EWAQ021BAWP [86/223] Setting of demand operation

Daikin EWAQ016BAWN [86/223] Setting of demand operation
ESIE11-05 Field Setting from Outdoor Unit
Functional Description 75
Setting of
demand
operation
By connecting the external contact input to the demand input of the outdoor unit external control
adaptor (optional), the power consumption of unit operation can be saved suppressing the
compressor operating condition.
*: However the demand operation does not occur in the following operation modes.
Startup control
Defrosting operation
Pump-down residual operation
If carrying out demand or low-noise input, connect the adaptor’s terminals as shown below.
A. When the demand operation is carried out by external contact (with the use of the
external control adaptor for outdoor unit).
1. Connect external control adaptor for outdoor unit and short-circuit terminals as required
(refer above figure).
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of external
low noise/demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1
level) and then set the setting condition to targeted mode.
B. When the normal demand operation is carried out. (Use of the external control
adaptor for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of alternate demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Setting content Setting method
Set item Condition Content External control adaptor Outdoor unit PCB
Demand 1
Mode 1
The compressor operates at
approx. 60% or less of
rating.
Short circuit “1” and “C” on
the terminal strip (TeS1).
Set item No. 32 to
“Demand 1”, and item No.
30 to “Level 1”.
Mode 2
The compressor operates at
approx. 70% or less of
rating.
Set item No. 32 to
“Demand 1”, and item No.
30 to “Level 2”.
Mode 3
The compressor operates at
approx. 80% or less of
rating.
Set item No. 32 to
“Demand 1”, and item No.
30 to “Level 3”.
Demand 2
The compressor operates at
approx. 40% or less of
rating.
Short circuit “2” and “C”.
Set item No. 32 to
“Demand 2”.
Demand 3 Forced thermostat OFF. Short circuit “3” and “C”.