Daikin EWAQ021BAWP [77/223] Mode changing procedure 1

Daikin EWAQ016BAWN [77/223] Mode changing procedure 1
Field Setting from Outdoor Unit ESIE11-05
66 Functional Description
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Mode changing
procedure 1
Mode changing
procedure 2
Setting mode 1
Monitor mode
H1P
Push the BS1(MODE button)
one time.
Blinking
MODE MODE
Off
H1P
Setting mode 2
MODE
On
H1P
Push and hold the BS1
(MODE button) for 5 seconds.
Push the BS1(MODE button) one time.
(Normal)
(V2761)
Using the MODE button, the modes can be changed as follows.
Check item selection
(SET button)
Contents display
Monitor mode
Setting mode 1
(Initial condition)
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Setting item selection
(SET button)
Setting mode 2
(Set): Select mode with BS2 (SET button) in each selection step.
Setting condition
selection (
SET button
)
Setting condition
(Contents) display
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Press BS3 (RETURN button) one time.
Press BS1 (MODE button) one time.
Press BS1 (MODE button) one time.
Press BS1(MODE button) one time.
Press BS1 (MODE button) for more than 5 sec.
(V2762)