Daikin EWYQ021BAWP [108/223] Symptom based troubleshooting

Daikin EWYQ021BAWP [108/223] Symptom based troubleshooting
ESIE11-05 Symptom-based Troubleshooting
Troubleshooting 97
1. Symptom-based Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start operation at all. Blowout of fuse(s) Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s) If the knob of any breaker is in
its OFF position, turn ON the
power supply.
If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
Power failure After the power failure is reset,
restart the system.
Open phase in power supply
cable
Check power supply. After that,
properly connect the power
supply cable, and then turn ON
the power supply.
2 The system starts operation but makes an
immediate stop.
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
3 The unit is turned on but is not heating/cooling as
expected.
The temperature setting is not
correct.
Check the controller set point.
Capacity shortage. Check if the cooling fan at the rear
of the switch box is working
properly.
Check if the unit is not installed in
a too hot location (> 30°C).
The water volume in the
installation is too low.
Make sure that the water volume
in the installation is above the
minimum required value.
The water flow is too low. Check that all shut-off valves of
the water circuit are completely
open.
Check if the water filter needs
cleaning.
Make sure there is no air in the
system (purge air).
Make sure that the expansion
vessel is not broken.
Check on the manometer that
there is sufficient water
pressure. The water pressure
must be > 0,3 bar (water is
cold); >> 0,3 bar (water is hot).
Blocked air inlet or outlet of indoor
or outdoor unit
Remove obstacle(s).
Enclosed outdoor unit(s) Remove the enclosure.
4 The system does
not operate.
The system stops and
immediately restarts operation.
If the OPERATION lamp on the
remote control turns ON, the
system will be normal. These
symptoms indicate that the
system is controlled so as not to
put unreasonable loads on the
system.
Normal operation. The system will
automatically starts operation
after a lapse of five minutes.
Pressing the TEMP ADJUST
button immediately resets the
system.
ON
OFF
Knob
Tripped
Circuit breaker