Daikin FXL63LVE [54/56] Selection procedure

Daikin FXL63LVE [54/56] Selection procedure
6
Systems • Introduction
53
• Introduction
6 Selection procedure
6-6 Refrigerant pipe selection
6-6-5 RSEYP16-30K
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
Maximum
allowable
length
Between outdoor and
indoor unit
Actual pipe length
Actual pipe length
Actual pipe length
Example of downstream indoor units
Pipe length between outdoor and indoor units 100m
Example unit 8 : a + b + c + d + e + s 100m
Example unit 8 : b + c + d + e + s 40m
Example in case of refnet joint C: indoor units 5 + 6 + 7 + 8
Between outdoor unit and the uppermost stream refrigerant branch kit
Select pipe size according to outdoor system.
Between two immediately adjacent refrigerant branch kits and BS unit
Select the proper pipe size based on the total capacity index of indoor units connected downstream, using
the following table.
Select connection pipe size according to the outdoor unit (table on the bottom left). Do not select a larger
pipe size.
Between BS unit and indoor unit
l
Pipe size for direct connection to indoor unit must be the same as the connection size of indoor unit.
Example for refrigerant branch using refnet joint and header (RSEYP30K)
Example in case of refnet joint B: indoor units 7 + 8
Example in case of refnet header: indoor units 1 + 2 + 3 +4+5+6
Example in case of refnet header: indoor units 1 +2+3+4+5+6+7+8
How to select the refnet header
Select the proper branch kit model based on the total capacity index of indoor units installed after
the header using the following table.
Branching is impossible between refnet header and indoor unit.
For systems with a total capacity of 640 and over,
connect a refnet joint branch.
In case of 2 pipes, please select KHRP26K-H series.
Example unit 6 : b + l 40m, Example unit 8 :m + n + p 40m Example unit 8 : o 40m
Example unit 6 : a + b + l 100m Example unit 8 : a + o 100m
Equivalent pipe length between outdoor and indoor units 125m (assume equivalent pipe length of refnet joint to be 0.5m, that of refnet header to be 1m, that of BS unit to be 4m, calculation purposes)
Pipe length between outdoor unit (main) and outdoor unit (sub)(Q) 5m
Difference in height between indoor units and outdoor units (H1) 50m ( 40m or less when oudoor unit is located in a lower position)
Difference in height between adjacent indoor units (H2) 15m
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) 5m
Pipe length from first refrigerant branch kit (either refnet joint or refnet header ) to indoor unit 40m
Difference in height
Equivalent length
Between outdoor unit (main) and outdoor unit
(sub)
Between outdoor and indoor units
Between adjacent indoor units
Between outdoor unit (main) and outdoor unit (sub)
Allowable
height length
Allowable length after the branch
Refrigerant branch kit selection
Pipe size selection
Pipe size = outer diameter x minimum wall thickness
(Unit; mm).
Use the included reducing joint which matches the pipe size.
Additional refrigerant to be charged
Calculation of additional refrigerant to be charged R (kg) is in function of the total length of liquid Iines L
Note
• Round off R to 1 decimal place
indoor capacity index
< 160
160 x < 330
330 x < 640
640 x
branch kit
KHRP25K18T
KHRP25K20T
KHRP25K40T + KHRP26K40T
KHRP25K75T + KHRP25K75T
indoor capacity index
100
x < 160
50
x < 100
160
x < 330
330
x < 480
480
x < 640
640
x < 700
x > 700
x < 50
Pipe size
Liquid pipe
ø6.4 x t0.8 ø9.5 x t0.8ø12.7 x t0.8
ø9.5 x t0.8
ø9.5 x t0.8
ø12.7 x t0.8
ø15.9 x t1.0
ø19.1 x t1.0
ø19.1 x t1.0
ø19.1 x t1.0
ø15.9 x t1.0
ø19.1 x t1.0
ø25.4 x t1.2
ø34.9 x t1.3
ø34.9 x t1.3
ø41.3 x t1.7
ø41.3 x t1.7
ø12.7 x t0.8
ø15.9 x t1.0
ø19.1 x t1.0
ø25.4 x t1.2
ø25.4 x t1.2
ø25.4 x t1.2
f34.9 x t1.3
Gas pipe
Suction
Discharge
Outdoor system name
RSEYP24K
RSEYP18-20K
RSEYP26K
RSEYP28-30K
RSEYP16K
Pipe size
Liquid pipe
ø15.9 x t1.0 ø28.6 x t1.2ø34.9 x t1.3
ø19.1 x t1.0
ø19.1 x t1.0
ø22.2 x t1.2
ø22.2 x t1.2
ø34.9 x t1.3
ø41.3 x t1.7
ø41.3 x t1.7
ø41.3 x t1.7
ø28.6 x t1.2
ø28.6 x t1.2
ø34.9 x t1.3
ø34.9 x t1.3
Gas pipe
Suction
Discharge
indoor capacity index
20 · 25 · 32 · 40
50 · 63 · 80
100 · 125
200
250
Pipe size
ø
6.4 x t0.8
ø
9.5 x t0.8
ø
9.5 x t0.8
ø
12.7 x t0.8
ø
12.7 x t0.8
ø
12.7 x t0.8
ø
15.9 x t1.0
ø
19.1 x t1.0
ø
25.4 x t1.0
ø
28.6 x t1.2
Liquid pipe
Gas pipe
a: ø
22.2 x 30m
d: ø
9.5 x 5m
b: ø
19.1 x 10m
c: ø
9.5 x 20m
e: ø
9.5 x 20m
f
: ø
9.5 x 5m
g: ø
9.5 x 15m
h: ø
9.5 x 5m
i
: ø
9.5 x 10m
j
: ø
9.5 x 5m
k: ø
9.5 x 20m
l
: ø
9.5 x 5m
m: ø
12.7 x 10m
n
: ø
12.7 x 5m
o
: ø
12.7 x 20m
p
: ø
6.4 x 9m
indoor capacity index
< 160
160 x < 330
330 x < 640
branch kit
KHRP25K18H (Max. 6 branches)
KHRP25K37H (Max. 8 branches)
KHRP25K40H
(Max. 8 branches)
+ KHRP26K40HP
R=
R= 30
x0.39 + 10x0.28 + 35x0.12 + 110x0.06 + 9x0.023 +1.0 = 31.27
a
bm+n+o pc+d+e+f+g+h
+i+j+k+l
31.3
0:RSEYP16, 18, 24, 26, 28
0.6:RSEYP20
1.0:RSEYP30
+
x0.39
To tal length
of ø22.2
liquid line
+
x0.28
To tal length
of ø19.1
liquid line
+
x0.19
To tal length
of ø15.9
liquid line
+
x0.12
To tal length
of ø12.7
liquid line
+
x0.06
To tal length
of ø9.5
liquid line
+
x0.023
To tal length
of ø6.3
liquid line
REFNET joint
( ~ )
BS unit
( ~ )
A
A G
F
B1
B1 B4
Indoor unit
( ~ )
18
Cool/Heat selection
possible ( ~ )
16
Cooling only
(
.
)
78
1
h
f
gi k
b
m
a
l
c
G
2
j
3 4
B
B2
o
n
5
B3
q
p
6
B4
C D
r
H2
H1
s
7
8
E
d e
H3
Q
Outdoor unit
REFNET joint
(
.
)
BS unit
( ~ )
A
A B
B5
B1 B5
Indoor unit
( ~ )
18
Cool/Heat selection
possible
( ~ ,
.
)
1 4 78
Cooling only
(
.
)
56
d
c
1
B1
H2
H1
H3
Q
am
b
Outdoor unit
f
e
2
B2
h
g
3
B3
j
i
4
B4
k
5
l
o
n
p
6 7
8
B
REFNET header
BS unit
( ~ )
B1 B6
Indoor unit
( ~ )
18
Cool/Heat selection
possible ( ~ )
16
Cooling only
(
.
)
78
H2
H1
H3
Q
a
Outdoor unit
i
h
4
B4
g
f
3
B3
e
d
2
B2
c
b
1
B1
k
j
5
B5
m
l
6
B6
n
7
o
8
REFNET header
(Unit : mm)
(Unit : mm)
How to select the refnet joint
When using refnet joints at the first branch counted from the outdoor unit side.
If the system capacity is < 500, use KHRP25K40T + KHRP26K40TP(Pipe size reducer).
If the system capacity is 500, use KHRP25K75T + KHRP25K75TP (Pipe size reducer).
For refnet joints other than the first branch, select the proper branch kit
model based on the total capacity index of the indoor units installed
after the first branch using the following table:
In case of 2 pipes, please select KHRP26K-T series
1
A
Outdoor
unit
Indoor
unit
Discharge gas pipe
(3 pipes) (2 pipes)
Suction gas pipe
Liquid pipe
Gas pipe
Liquid pipe
BS
unit
indoor unit
refnet joint
refnet header