Daikin RXYQ26PY1 [247/398] E3 outdoor unit actuation of high pressure switch

Daikin RXYQ50PHY1 [247/398] E3 outdoor unit actuation of high pressure switch
Troubleshooting by Indication on the Remote Controller Si34-601A
236 Troubleshooting
3.14
E3
Outdoor Unit: Actuation of High Pressure Switch
Remote
Controller
Display
E3
Applicable
Models
RXYQ5P~54P
Method of
Malfunction
Detection
Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Decision
Conditions
Error is generated when the HPS activation count reaches the number specific to the operation
mode.
(Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 2.85MPa
Supposed
Causes
Actuation of outdoor unit high pressure switch
Defect of High pressure switch
Defect of outdoor unit PC board
Instantaneous power failure
Faulty high pressure sensor