Daikin RXYQ26PY1 [274/398] Troubleshooting

Daikin RXYQ26PY1 [274/398] Troubleshooting
Si34-601A Troubleshooting by Indication on the Remote Controller
Troubleshooting 263
Troubleshooting
A
Power ON
Power OFF
Power OFF
Power ON
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
Check the compressor motor
coil for any broken wire.
The insulation
resistance is low (i.e.,
not more than
100k.)
Some phase has a
broken wire.
The power
transistor has an
abnormality.
Restart the
compressor, and then
check whether or not
the malfunction
recurs.
Restart the
compressor, and then
check whether or not
the malfunction
recurs.
Repalce the compressor.
A3P: Replace the inverter
PCB.
Normal
On-site causes such as
instantaneous power
failure or open phase
Conduct checks and
diagnosis of the
compressor.
End of work
Replace the compressor.
Conduct checks and
diagnosis of the
compressor.
Check the power transistor on
the inverter PC board using a
multiple tester. [For details,
refer to information in the
"Check for power transistor"
in Page 350, 351.
Make wire connections
according to the Wiring Diagram.
Replace the inverter PCB.