Daikin RXYQ48PY1 [33/38] Attached piping

Daikin RXQ5PY1 [33/38] Attached piping
6463
STANDARD SPECIFICATIONS
OPTIONS
Indoor unit
Type Ceiling mounted duct type
Model
Power supply
Air filter
Cooling capacity *1
Heating capacity *1
Product mass
Sound level *3
kcal/h
FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
V1: 1 phase 220-240V (also required for indoor units), 50 Hz
Indoor unit
Model
Operation remote controller
FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
BRC1C62
DCS302CA61
DCS301BA61
DST301BA61
KRP2A61
KRP4A51
12,000 19,300 24,100
7,700 12,000 15,000
380
X
1
18 28 35
185 225 205
*2
9.5 (flare)
15.9 (flare) 19.1 (brazing) 22.2 (brazing)
KAFJ371L140 KAFJ371L280
KAFJ372L140 KAFJ372L280
KAFJ373L140 KAFJ373L280
KDJ3705L140 KDJ3705L280
PS1B female thread
86 123
42 47
RX(Y)Q8–54PY1, RX(Y)Q16–50PHY1 RX(Y)Q10–54PY1, RX(Y)Q16–50PHY1
kcal/h
Dimensions (H
X
W
X
D) 470
X
744
X
1,100 470
X
1,380
X
1,100
Btu/h
47,800 76,400 95,500
kW
14.0 22.4 28.0
30,400 47,400 59,400Btu/h
8.9 13.9 17.4
kW
mm
Casing Galvanised steel plate
W
X
Number
of units
m
3
/min
Pa
Drain
mm
mm
mm
kg
dB(A)
Motor output
Air flow rate
635 988 1,236
cfm
Fan
Refrigerant
piping
External static pressure *4
Liquid
Gas
Connectable outdoor units *5 *6
Operating limit
(Fan mode operation between 15 and 19°C)
19 to 43°C
-5 to 15°C
Cooling
Heating
Range of the discharge temperature *7
13 to 25°C
18 to 30°C
Cooling
Heating
Operation/control
Filters
Central remote controller
Long-life replacement filter
Colorimetry method 65%
Colorimetry method 90%
High-efficiency
filter
Filter chamber *1
KRP1B61Adaptor for wiring
KDU30L250VEDrain pump kit
Unified ON/OFF controller
Schedule timer
Wiring adaptor for electrical appendices (1)
Wiring adaptor for electrical appendices (2)
Notes: *1. Filter chamber has a suction-type flange. (Main unit does not.)
• Dimensions and weight of the equipment may vary depending on the options used.
• Some options may not be usable due to the equipment installation conditions, so please confirm prior to ordering.
• Some options may not be used in combination.
• Operating sound may increase somewhat depending on the options used.
Notes: *1. Specifications are based on the following conditions;
• Cooling: Outdoor temp. of 33°CDB, 28°CWB (68% RH), and discharge temp. of 18°CDB. • Heating: Outdoor temp. of 0°CDB, -2.9°CWB (50% RH), and discharge temp. of 25°CDB.
• Equivalent reference piping length: 7.5 m (0 m horizontal) • At 220 V.
*2. An intake filter is not supplied, so be sure to install the optional long-life filter or high-efficiency filter.
Please mount it in the duct system of the suction side. Select its colorimetric method (gravity method) 50% or more.
*3. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.
These values (measured at 220 V) are normally somewhat higher during actual operation as a result of ambient conditions.
*4. Values measured at 220 V.
*5. Within the range that the total capacity of indoor units is 50 to 100%, it is possible to connect to the outdoor unit.
*6. It is not possible to connect to the 5 HP outdoor unit.
*7. Local setting mode. Not displayed on the remote controller.
• This equipment cannot be incorporated into the remote group control of the VRV system.
DIMENSIONS
*
These diagrams are based on FXMQ200 and FXM250QMFV1.
FXMQ200MFV1
FXMQ125MFV1
Model Gas piping diameter
15.9
19.1 attached piping
Liquid piping diameter
9.5
9.5
Local connection piping size
1
Liquid pipe connection
2
Gas pipe connection
3
Drain piping connection
4
Electric parts box
5
Ground terminal
6
Name plate
7
Power supply wiring connection
8
Transmission wiring connection
9
Hanger bracket
10
Discharge companion flange
11
Water supply port
12
Attached piping (Note. 1)
2
FXMQ250MFV1
22.2 attached piping 9.5
Table of dimensions
FXMQ200MFV1
FXMQ125MFV1
Model A B C
744 685 5X100=500
1380 1296 11X100=1100
D
20- 4.7 hole
32- 4.7 hole
FXMQ250MFV1
1380 1296 11X100=1100 32- 4.7 hole
(All around)
650 or more
(Service space)
Inspection hole 600 or more
1148
1100 or more
(Service space)
Approx.
150
9
10
C
A
B
D
A View
3
X
100=300
50
470
Suction side (Note.2)
760
1100
613
25146
11
Discharge side
30
3
B View
360
250
3
X
100=300
330
B View
390
30
296
25
630
5
X
100=500
600
20
-
7 hole
(All around)
8
360
200
250
346
10
-M5
hole
(All around)
2X200=400
580
630
7
61
Notes:
1. The attached piping in the diagram is for FXMQ200MFV1 and
FXMQ250MFV1 only. The gas piping connection port ( in the
diagram) has a different bore form with FXMQ125MFV1.
2. An air filter is not supplied with this unit. Be sure to mount an air
filter in the suction side.[Use a filter with dust collection efficiency
of at least 50% (gravimetric method). This is available as an option.]
3. For outdoor ducts, be sure to provide heat insulation to prevent
condensation.
FXMQ125MFV1
A View A View
1230
11
X
100=1100
1200
245
390
30
60
296
25
360
250
3
X
100=300
330
32
-
7 hole
(All around)
12
8
1004
5X200=1000
1230
16
-M5
hole
(All around)
360
200
250
330
B View (For FXMQ250MFV1)
7
5X200=1000
1230
580
360
200
250
330
16
-M5
hole
(All around)
B View (For FXMQ200MFV1)
7
FXMQ200/250MFV1
FXMQ125/200/250MFV1
Air Treatment Equipment Lineup