Daikin REMQ14PY1 [286/491] Caution be su re to t u rn off power s witch b efore connect or di s connect connector or p a rt s d a m a ge m a y b e occ u rred

Daikin REMQ16PY1 [286/491] Caution be su re to t u rn off power s witch b efore connect or di s connect connector or p a rt s d a m a ge m a y b e occ u rred
6L(1%( 7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWURO
7URXEOHVKRRWLQJ 
7URXEOHVKRRWLQJ
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Provide 220~240V power
supply.
YES
NO
Is power supply
220~240V provided?
Replace the limit switch
connecting cable.
Replace indoor unit PC board.
Replace the power supply
connecting cable.
Replace swing motor.
Take the cam mechanism
apart, reassemble and turn on
again.
YES
NO
YES
YES
NO
YES
NO
Connect the connector to X9A
and turn on again.
Replace indoor unit PC board.
NO
NO
YES
NO
YES
NO
YES
YES
NO
Replace s
wing motor.
(V2780)
Indoor unit
is a model equipped
with a swing flap
function
The
swing motor works
when the power supply is
turned off and then
back on.
After
turning the
swing-flap ON
and then stopping
with the remote control,
the voltage of X6A of the
indoor unit PC board is 220 ~
240 VAC (60 Hz) / 220 VAC
(50 Hz) when turned on
again (within 30
seconds of
turning on
again).
The
connecting cable has no
continuity.
When
the air flow
direction flap's cam
mechanism is disconnected
from the swing motor, operation
is normal when turned
on again.
The
connector is
connected to X9A of the
indoor unit PC
board.
The limit switch
functions normally.
The
connecting cable is
short-circuited or
disconnected.