7URXEOHVKRRWLQJE\,QGLFDWLRQRQWKH5HPRWH&RQWURO 6L(1%(
 7URXEOHVKRRWLQJ
7URXEOHVKRRWLQJ
Continued from the previous page.
(Start failure due to aged operation.)
Refrigerant is
sleeping. ( The unit is out
of power supply for more
than 6 hours.)
Check if the
insulation resistance of the
compressor is 100kΩ or
over.
Broken
inside the compressor
Cancel the sleeping state of
refrigerant.
Replace the inverter compressor.
Replace the inverter compressor.
Replace the compressor inverter
PC board.
Recheck the compressor/
refrigerant circuit.
NO
NO
NO
YES
NO
YES
YES
YES
Check 4
Check if the power
transistor is normal.
Check 4
: Referring to the information on P349.