Daikin RXYQ52PAYL [282/452] Indoor unit malfunction of capacity determination device
Troubleshooting by Indication on the Remote Controller Si34-803_B
271 Troubleshooting
3.9
AJ
Indoor Unit: Malfunction of Capacity Determination
Device
Remote
controller display
AJ
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PCB, and whether the value is normal or abnormal is
determined.
Malfunction
Decision
Conditions
Operation and:
When the capacity code is not saved to the PCB, and the capacity setting adaptor is not
connected.
When a capacity that does not exist for that unit is set.
Supposed
Causes
You have forgotten to install the capacity setting adaptor.
Defect of indoor unit PCB
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Install a capacity setting adaptor.
Replace the indoor unit PCB.
NO
YES
YES
NO
Replace the indoor unit PCB.
The indoor
unit PCB was replaced
with a spare
PCB.
The
capacity setting
adaptor need to be installed
when replacing the
PCB.