Daikin RXYQ54PAYL [286/452] When the gas pipe thermistor becomes disconnected or shorted while the unit is running
Troubleshooting by Indication on the Remote Controller Si34-803_B
275 Troubleshooting
3.12
C5
Indoor Unit: Malfunction of Thermistor (R3T) for Gas
Pipe
Remote
Controller
Display
C5
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Decision
Conditions
When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Supposed
Causes
Defect of indoor unit thermistor (R3T) for gas pipe
Defect of indoor unit PCB
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.426.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Remove the thermistor from
the indoor unit PCB, and
then insert it again.
Remove the thermistor from
the indoor unit PCB, and
then make resistance
measurement of the thermistor
using a multiple meter.
Normal (The malfunction is
caused by faulty contact.)
YES
NO
Replace the indoor unit PCB.
YES
Is the
thermistor normal?
Replace the thermistor (R3T).
NO
5 k to 90 k