Daikin RXYQ14PAYL [290/452] Indoor unit malfunction of thermostat sensor in remote controller
Troubleshooting by Indication on the Remote Controller Si34-803_B
279 Troubleshooting
3.16
CJ
Indoor Unit: Malfunction of Thermostat Sensor in
Remote Controller
Remote
Controller
Display
CJ
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Malfunction detection is carried out by temperature detected by remote controller air
temperature thermistor. (Note:)
Malfunction
Decision
Conditions
When the remote controller air temperature thermistor becomes disconnected or shorted while
the unit is running.
Supposed
Causes
Defect of remote controller thermistor
Defect of remote controller PCB
Troubleshooting
Note: In case of remote controller thermistor malfunction, unit is still operable by suction air thermistor
on indoor unit.
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.426.
Clear the malfunction code
history. (While in inspection
mode,
press and hold the
“ON/OFF”
button for a period of
4 seconds or more.)
Is "CJ"
displayed on the remote
controller?
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Replace the remote
controller.
External factor other than
equipment malfunction.
(for example, noise etc.)
NO