Daikin RXYQ22PAYL [313/452] Outdoor unit malfunction of subcooling heat exchanger gas pipe thermistor r5t
Si34-803_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 302
3.33
J9
Outdoor Unit: Malfunction of Subcooling Heat
Exchanger Gas Pipe Thermistor (R5T)
Remote
Controller
Display
J9
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by subcooling heat exchanger
gas pipe thermistor.
Malfunction
Decision
Conditions
When the subcooling heat exchanger gas pipe thermistor is short circuited or open circuited.
Supposed
Causes
Faulty subcooling heat exchanger gas pipe thermistor (R5T)
Faulty outdoor unit PCB
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.426.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R5T) from outdoor unit
PCB normal?
(1.8k to
800k)
Replace the outdoor unit PCB
(A1P).
Connect the connector and
operate the unit again.
NO
NO
Replace the thermistor (R5T).
YES
YES
Is
the connector
for subcooling heat
exchanger gas pipe
thermistor connected to
X30A on outdoor
unit PCB
(A1P)?