Daikin RXYQ14PAYL — устранение неисправностей термистора в наружном блоке [307/452]

Daikin RXYQ26PAYL [307/452] Malfunction decision conditions
Si34-803_B Troubleshooting by Indication on the Remote Controller
Troubleshooting 296
3.27
H9
Outdoor Unit: Malfunction of Thermistor (R1T) for
Outdoor Air
Remote
Controller
Display
H9
Applicable
Models
RXYQ5P(A)~54P(A)
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Decision
Conditions
When the outside air temperature thermistor has short circuit or open circuit.
Supposed
Causes
Defect of thermistor (R1T) for outdoor air
Defect of outdoor unit PCB (A1P)
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P.426.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the outdoor
unit PCB.
(1.8k to
800k)
Connector is
connected to X18A of
outdoor unit PCB
(A1P).
Replace the outdoor unit PCB
(A1P).
Connect the connector and turn on
again.
NO
NO
Replace the thermistor (R1T).
YES
YES