Daikin REYQ22PY1 [295/438] Troubleshooting compressor inspection

Daikin REYQ22PY1 [295/438] Troubleshooting compressor inspection
Troubleshooting by Indication on the Remote Controller Si37-701
284 Troubleshooting
Troubleshooting Compressor inspection
Correct the wiring and
connection.
Replace inverter
compressor.
Replace inverter
compressor.
Replace inverter PC board
(A2P).
Continue operation.
Momentary power failure
is possible.
Replace compressor lead
wires.
Open the stop valve.
NO
NO
NO
YES
YES
NO
NO
NO
YES
YES
YES
YES
NO
NO
Power OFF
Power OFF
and the Power
ON again
Check if
the stop valve is
open.
Check if
the compressor lead
wires are normal.
Check if the
wiring and connection to
the compressor
are normal.
Insulation
resistance of the compressor
is 100 k or
below.
Check 4
Check if the power transistor
is normal.
Failure
occurs again after restarting
the unit.
Failure
occurs again after restarting
the unit.
Compressor
coils are disconnected.
YES
YES
Replace inverter PC board (A2P).
Continue operation.
Replace inverter
compressor.
(
(
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check 4
: Referring to the information on P339.