Daikin RXYMQ48MVJU [11/31] Caution
![Daikin RXYMQ48MVJU [11/31] Caution](/views2/1718439/page11/bgb.png)
Installation EDUS39-606A-N
10 Installation of Outdoor Units
• Before touching electrical parts, turn off the power.
• When installing or relocating the system, be sure to
keep the refrigerant circuit free from substances
other than the specified refrigerant (R-410A) such as
air.
Any presence of air or other foreign substance in the
refrigerant circuit causes an abnormal pressure rise or
rupture, resulting in injury.
• Do not reconstruct or change the settings of the pro-
tection devices.
If the pressure switch, thermal switch, or other protection
device is shorted and operated forcibly, or parts other
than those specified by Daikin are used, fire or explosion
may result.
• Placing a flower vase or other containers with water
or other liquids on the unit could result in a shock
hazard or fire if a spill occurs.
• Do not touch the switch with wet fingers.
Touching a switch with wet fingers can cause electric
shock.
• Be sure to install a ground leakage breaker.
Failure to install a ground leakage breaker may result in
electric shocks, or fire.
• Heat exchanger fins are sharp enough to cut.
To avoid injury wear glove or cover the fins when working
around them.
• Do not touch the air outlet or horizontal blades while
the swing flap is in operation because fingers can
get caught and injured.
• Do not allow children to play on or around the unit as
they could be injured.
• Refrigerant pipes may be very hot or very cold dur-
ing or immediately after operation.
Touching them could result in burns or frostbite. To avoid
injury give the pipes time to return to normal temperature
or, if you must touch them, be sure to wear proper gloves.
• While following the instructions in this installation manual,
install drain piping in order to ensure proper drainage and
insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and
property damage.
• Be very careful about product transportation.
• Do not touch the refrigerant pipes during and imme-
diately after operation.
During and immediately after operation, the refrigerant
pipes may be hot and may be cold, depending on the
condition of the refrigerant flowing through the refrigerant
piping, compressor, and other refrigerant cycle parts.
Your hands may suffer burns or frostbite if you touch the
refrigerant pipes.
• Do not remove the front panel because some parts
inside are dangerous to touch. In addition, some
parts may be damaged by touching them. For check
-
ing and adjust internal parts, contact your dealer.
• Do not turn off the power immediately after stopping
operation.
Always wait at least five minutes before turning off the
power. Otherwise, water leakage and trouble may occur.
• Do not use a charging cylinder.
Using a charging cylinder may cause the refrigerant to
deteriorate.
• The refrigerant R-410A requires strict cautions for
keeping the system clean, dry and tight.
A. Clean and dry
Foreign materials (including mineral oils such as
SUNISO oil or moisture) should be prevented from get
-
ting mixed into the system.
B. Tight
CAUTION
R-410A does not contain any chlorine, does not destroy
the ozone layer, and does not reduce the earth’s protec-
tion against harmful ultraviolet radiation.
R-410A can contribute slightly to the greenhouse effect if
it is released. Therefore we should take special attention
to check the tightness of the installation.
Read Section 6, REFRIGERANT PIPING WORK care-
fully and follow these procedures correctly.
• Since R-410A is a mixed refrigerant, the required
additional refrigerant must be charged in its liquid
state. (If the refrigerant is charged in a state of gas,
its composition changes and the system will not
work properly.)
The indoor unit is for R-410A. See the catalog for indoor
unit models which can be connected.
(Normal operation is not possible when connected to other
units.)
• For installation of the indoor units, refer to the instal-
lation manual supplied together with each indoor
unit.
• Check the unit stand for damage on a continuous
basis, especially if it has been in use a long time. If
left in a damaged condition, the unit may fall and
cause injury.
• Never operate the air conditioner with the discharge
pipe thermistor (R3T), suction pipe thermistor (R2T)
and pressure sensors (S1NPH, S1NPL) removed.
Such operation may burn out the compressor.
• Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the cus-
tomer to keep the area around the unit clean.
NOTE
• Install the indoor and outdoor units, power supply wiring
and transmission wiring at least 3.5 ft. away from televi
-
sions or radios in order to prevent image interference or
noise.
Depending on the radio waves, a distance of 3.5ft. may not
be enough to eliminate the noise.
• Dismantling of the unit, treatment of the refrigerant, oil
and eventual other parts, should be done in accor-
dance with the relevant local and national regulations.
• Do not use the following tools that are used with con-
ventional refrigerants: Gauge manifold, charge hose,
gas leak detector, reverse flow check valve, refrigerant
charge base, vacuum gauge, refrigerant recovery
equipment.
Содержание
- Installation of outdoor units 2
- Center of gravity 3
- Rxymq36 48mvju 3
- Layout example 4
- Refnet pipe system 4
- Sample systems 4
- Field refrigerant piping 5
- For gas and liquid branch pipes 5
- Refnet joints 5
- Refnet joints and headers 5
- Refnet header 6
- Edus39 606a n refnet pipe 8
- Gas side 8
- Installation of outdoor units 7 8
- Khrp26m22h 8
- Khrp26m22t 8
- Khrp26m33t 8
- Liquid side 8
- Refnet header branch kit 8
- Refnet joint branch kit 8
- Refnet pipe 8
- D3k03630b 9
- Gas side liquid side 9
- Installation of outdoor units 9
- Insulation insulation 9
- Khrp26m33h 9
- Refnet pipe edus39 606a n 9
- Danger 10
- Installation 10
- Safety considerations rxymq m 10
- Caution 11
- Accessories 12
- Before installation 12
- Combination 12
- Cooling heating 12
- Electrical specifications 12
- Introduction 12
- Main components 12
- Optional accessories 12
- Standard operation limit 12
- Technical specifications 12
- Selection of installation location 13
- Danger 14
- 1 when one outdoor unit is installed individually 16
- 2 when two or more outdoor units are installed side by side 16
- Close the area under the frame so that the outlet air does not bypass there 16
- Close the area under the frame so that the outlet air does not bypass there 2 when only two outdoor units are installed side by side 16
- Edus39 606a n installation 16
- Installation of outdoor units 15 16
- Only two outdoor units can be installed side by side 16
- The dimensional relationship between h l and a is as shown in the following table 16
- The dimensional relationship between h l and a is as shown in the table below 16
- When an obstruction is also present in the upward area 1 when one outdoor unit is installed individually 16
- When an obstruction is present also in the upward area 16
- When an obstruction on the air outlet side is lower than the out door unit there is no restriction in the height of obstruction on the air inlet side 16
- When the upward area is open 16
- Cautions on installation 18
- Refrigerant piping work 18
- Danger 19
- Piping connection 19
- Protection of piping 19
- Selection of piping material 19
- Caution 20
- Branch with refnet header 21
- Branch with refnet joint 21
- Connection of 5 indoor units 21
- Example of connection 21
- Installation edus39 606a n 21
- Installation of outdoor units 21
- Additional refrigerant charge 22
- Airtight test and vacuum drying 22
- Danger 23
- Electrical wiring work 23
- Using a spanner on the valve cap and the valve body could cause a refrigerant leak 23
- Caution 24
- Connection example of whole system wiring 24
- Routing power supply wiring and transmission wiring 24
- Caution 25
- Power supply wiring connection procedure 25
- When using shield wire 25
- Caution 26
- Restrictions and cautions for wiring between units 26
- Transmission wiring connection procedure 26
- Caution 27
- Checks after completion of work 27
- Power on and check operation 27
- Checks in normal operation 28
- Caution 29
- Caution for refrigerant leaks 29
- Danger 29
- Edus39 606a n checks after completion of work 29
- Installation of outdoor units 28 29
- Or the weight in lb of the refrigerant gas in 1f 29
- Refrigerant gas is heavier than air and replaces oxygen a massive leak could lead to oxygen depletion especially in basements and an asphyxiation hazard could occur lead ing to serious injury or death 29
- The installer and system specialist must follow proce dures to prevent leakage according to local regulations or standards the following standards may be applicable if local regulations are not available 29
- The vrv system like other air conditioning systems uses r 410a which is an entirely safe non toxic non combustible refrigerant nevertheless care must be taken to ensure that air conditioning facilities are installed in rooms large enough to ensure that in the unlikely event of a major leak the maxi mum concentration level of refrigerant gas is not exceeded maximum concentration level the maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak the unit of measurement of the concentration is lb f 29
- Volume of the occu pied space 29
Похожие устройства
- SilverStone SST-AR01-V2.1 (adds AM4 support & black fan frame) Инструкция по эксплуатации
- SilverStone SST-AR01-V2.1 (adds AM4 support & black fan frame) Документация
- Daikin RXYMQ36MVJU Сервис мануал
- Daikin RXYMQ48MVJU Сервис мануал
- Daikin RZQ18PVJU Спецификация
- Daikin RXYMQ36MVJU Инструкция по эксплуатации
- Daikin RXYMQ48MVJU Инструкция по эксплуатации
- Daikin RZQ18PVJU Руководство по вводу в эксплуатацию
- Daikin RZQ24PVJU Спецификация
- Daikin RZQ30PVJU Спецификация
- Daikin RZQ18PVJU Инструкция по монтажу
- Daikin RZQ24PVJU Руководство по вводу в эксплуатацию
- Daikin RZQ18PVJU Технические данные
- Daikin RZQ30PVJU Руководство по вводу в эксплуатацию
- Daikin RZQ18PVJU Сервис мануал
- Daikin RZQ24PVJU Инструкция по монтажу
- Daikin RZQ30PVJU Инструкция по монтажу
- Daikin RZQ24PVJU Технические данные
- SilverStone SST-AR01 Инструкция по эксплуатации
- Daikin RZQ30PVJU Технические данные