Daikin VAM500FJVE [46/84] Indoor air thermistor error

Daikin VAM500FJVE [46/84] Indoor air thermistor error
SiE00-01 Troubleshooting
Troubleshooting 37
1.4 Indoor Air Thermistor Error
Remote Controller
LCD Display
Error Code 66
66
44
44
Inspection Unit No. 5
LED Indication Remote Controller 4 Main Unit 5
Error Detection
Method
Temperature detected by inside air temperature sensor is used to detect errors.
Error Generating
Conditions
When value detected by inside air temperature sensor is -40ºC or below (open circuit) or 70ºC or higher
(shorting).
Possible Causes Faulty sensor
Broken wire
Faulty control PCB
Faulty contact in connector
Troubleshooting
Note: Note 1:
Refer to the thermistor temperature - resistance conversion table when measuring resistance.
Thermistor temperature - resistance conversion table
If measured value deviates significantly from above values, thermistor is faulty.
Use tester to check resistance
Remove Indoor air
thermistor (R1T) from
X12A (3P) on control
PCB, and measure
resistance.
Is
thermistor
normal?
Note 1
YES
NO
Replace indoor air
thermistor.
If there is no faulty
contact, replace
control PCB.
(HF003)
Thermistor
temperature
Sensor resistance Thermistor
temperature
Sensor resistance
-10°C or less 108k or more 22°C Approx. 23k
-5°C Approx. 85k 24°C Approx. 21k
0°C Approx. 66k 26°C Approx. 19k
5°C Approx. 51k 28°C Approx. 18k
10°C Approx. 40k 30°C Approx. 16k
14°C Approx. 33k 35°C Approx. 13k
16°C Approx. 30k 40°C Approx. 11k
18°C Approx. 27k 50°C or more 7k or less
20°C Approx. 25k