Daikin VAM2000FAVE [11/81] Product introduction

Daikin VAM2000FAVE [11/81] Product introduction
1. Product introduction
10 1.4 Selection Procedures
1
1.4
Required
ventilating AFR
per person
(m
3
/ h / person)
Area per person
(m
2
/ person)
Model Name
Frequency Air Flow Rate
Application area (m
2
)
Hz L H
40
3
VAM 150FAVE
50 110 150 8.3 11.3
60 110 150 8.3 11.3
VAM 250FAVE
50 155 250 11.6 18.8
60 145 250 10.9 18.8
VAM 350FAVE
50 230 350 17.3 26.3
60 210 350 15.8 26.3
VAM 500FAVE
50 350 500 26.3 37.5
60 300 500 22.5 37.5
VAM 650FAVE
50 500 650 37.5 48.8
60 440 650 33.0 48.8
VAM 800FA5VE
50 670 800 50.3 60.0
60 660 800 49.5 60.0
VAM1000FA5VE
50 870 1000 65.3 75.0
60 800 1000 60.0 75.0
VAM1500FA5VE
50 1200 1500 90.0 112.5
60 1200 1500 90.0 112.5
VAM2000FA5VE
50 1400 2000 105.0 150.0
60 1400 2000 105.0 150.0
5
VAM 150FAVE
50 110 150 13.8 18.8
60 110 150 13.8 18.8
VAM 250FAVE
50 155 250 19.4 31.3
60 145 250 18.1 31.3
VAM 350FAVE
50 230 350 28.8 43.8
60 210 350 26.3 43.8
VAM 500FAVE
50 350 500 43.8 62.5
60 300 500 37.5 62.5
VAM 650FAVE
50 500 650 62.5 81.3
60 440 650 55.0 81.3
VAM 800FA5VE
50 670 800 83.8 100.0
60 660 800 82.5 100.0
VAM1000FA5VE
50 870 1000 108.8 125.0
60 800 1000 100.0 125.0
VAM1500FA5VE
50 1200 1500 150.0 187.5
60 1200 1500 150.0 187.5
VAM2000FA5VE
50 1400 2000 175.0 250.0
60 1400 2000 175.0 250.0
10
VAM 150FAVE
50 110 150 27.5 37.5
60 110 150 27.5 37.5
VAM 250FAVE
50 155 250 38.8 62.5
60 145 250 36.3 62.5
VAM 350FAVE
50 230 350 57.5 87.5
60 210 350 52.5 87.5
VAM 500FAVE
50 350 500 87.5 125.0
60 300 500 75.0 125.0
VAM 650FAVE
50 500 650 125.0 162.5
60 440 650 110.0 162.5
VAM 800FA5VE
50 670 800 167.5 200.0
60 660 800 165.0 200.0
VAM1000FA5VE
50 870 1000 217.5 250.0
60 800 1000 200.0 250.0
VAM1500FA5VE
50 1200 1500 300.0 375.0
60 1200 1500 300.0 375.0
VAM2000FA5VE
50 1400 2000 350.0 500.0
60 1400 2000 350.0 500.0
Note:
AFR Air Flow Rate

Содержание