■English 8
5.
Refilling the refrigerant
Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the gas pipe in liquid form.
It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
1) Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon
attached” displayed on it.)
2) Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.
6.
Charging with refrigerant
• If the total length of piping for all rooms exceeds 20m, additionally charge with (R410A) 20g of refrigerant for each addi-
tional meter of piping.
NOTE:
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate
official national language on the unit. Therefor an additional multilingual fluorinated greenhouse gases label is supplied
with the unit.
Sticking instructions are illustrated on the backside of that label.
CAUTION
• Even though the stop valve is fully closed, the refrigerant may slowly leak out; do not leave the flare nut removed for a long
period of time.
• Do not overfill with refrigerant. This will break the compressor.
Filling a cylinder with an attached siphon
Stand the cylinder upright when filling.
There is a siphon pipe inside, so the
cylinder need not be upside-down to
fill with liquid.
Filling other cylinders
Turn the cylinder upside-down
when filling.
3
5
6
2
1
4
Please fill in with indelible ink,
n
1
the factory refrigerant charge of the product,
n
2
the additional refrigerant amount charged in the field and
n
1 + 2
the total refrigerant charge
on the refrigerant charge label supplied with the product.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Do not vent gases into the atmosphere.
Refrigerant type:
R410A
GWP
(1)
value: 1975
(1)
GWP = global warming potential
1 factory refrigerant charge of the product: see unit name plate
2 additional refrigerant amount charged in the field
3 total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and manifold for charging
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve
cover).
01_EN_3P210724-1F.fm Page 8 Tuesday, October 30, 2012 10:39 AM
Содержание
- Installation manual 1
- Models 1
- Mxs40g2v1b 2mks40g2v1b 2mxs40h2v1b 2mks40h2v1b 2mxs40h3v1b 2mks50g2v1b 2mxs50g2v1b 2mks50h2v1b 2mxs50h2v1b 2mxs50h3v1b 2amx40f2v1b 2amx40g2v1b 2amx40g3v1b 2amx50f2v1b 2amx50g2v1b 2amx50g3v1b 1
- R410a split series 1
- Umeda center bldg 2 4 12 nakazaki nishi kita ku osaka 530 8323 japan 2
- Caution 5
- English 5
- Safety precautions 5
- Warning 5
- Accessories 6
- Caution 6
- English 2 6
- Precautions for selecting the location 6
- Also insulate the connection on the outdoor unit 7
- Caution 7
- Clamping material 7
- English 7
- Indoor outdoor unit installation drawings 7
- Indoor outdoor unitinstallation drawings 7
- Insulation tube 7
- Service lid tape 7
- Use tape or insulating material on all connections to prevent air from getting in between the copper piping and the insulation tube be sure to do this if the outdoor unit is installed above 7
- Connections connection port 8
- English 4 8
- How to use reducers 8
- Installation 8
- Precautions on installation 8
- English 9
- If the outdoor unit is positioned higher than the indoor units if the outdoor unit is positioned otherwise if lower than one or more indoor units 9
- Outdoor unit installation guideline 9
- Piping to each indoor unit 20m max 9
- Selecting a location for installation of the indoor units 9
- Selecting a location for installation ofthe indoor units 9
- The maximum allowable length of refrigerant piping and the maximum allowable height difference between the outdoor and indoor units are listed below the shorter the refrigerant piping the better the performance connect so that the piping is as short as possible shortest allow able length per room is 3m 9
- Total length of piping between all units 30m max 9
- Wall facing one side 9
- Walls facing three sides 9
- Walls facing two sides 9
- Where a wall or other obstacle is in the path of outdoor unit s inlet or outlet airflow follow the installation guidelines below for any of the below installation patterns the wall height on the exhaust side should be 1200mm or less 9
- Caution 10
- Drain work only heat pump models 10
- Installing outdoor unit 10
- Refrigerant piping 10
- Refrigerant piping work 10
- Purging air and checking gas leakage 11
- Refrigerant piping work 11
- Warning 11
- Caution 12
- Charging with refrigerant 12
- Important information regarding the refrigerant used 12
- Refilling the refrigerant 12
- English 13
- Precautions for laying refrigerant piping 13
- Refrigerant piping work 13
- Warning 13
- Caution 14
- Forced cooling operation 14
- Pump down operation 14
- Caution 15
- English 15
- Good wrong good wrong 15
- Warning 15
- Wiring 15
- Caution 16
- English 12 16
- Maximum power input limitation setting 16
- Warning 16
- Caution 17
- Econo mode prohibition setting 17
- English 17
- Warning 17
- English 14 18
- Items to check 18
- Trial operation and testing 18
- P210724 1f m07b062f 19
Похожие устройства
- Daikin 2MXS40H3V1B2 Инструкция по монтажу
- Daikin 2MXS50H2V1B Инструкция по монтажу
- Daikin 2MXS50H3V1B Инструкция по монтажу
- Daikin 2MXS50H2V1B Сервис мануал
- Daikin 2MXS50H3V1B2 Инструкция по монтажу
- Daikin 3MXM40N2V1B Руководство по эксплуатации
- Daikin 3MXM40N2V1B Инструкция по монтажу
- Daikin 3MXM40N2V1B Руководство по монтажу
- Daikin 3MXM52N2V1B Руководство по эксплуатации
- Daikin 3MXM52N2V1B Инструкция по монтажу
- Daikin 3MXM52N2V1B Справочное руководство для монтажника
- Daikin 3MXM68N2V1B Руководство по эксплуатации
- Daikin 3MXM40N2V1B Справочное руководство для монтажника
- Daikin 3MXM68N2V1B Инструкция по монтажу
- Daikin 3MXM52N2V1B Руководство по монтажу
- Daikin 3MXM68N2V1B Руководство по монтажу
- Daikin 3MXM68N2V1B Справочное руководство для монтажника
- Daikin 3MXM40N2V1B7 Справочное руководство для монтажника
- Daikin 3MXM40N2V1B7 Инструкция по монтажу
- Daikin 3MXM52N2V1B7 Справочное руководство для монтажника