Daikin RKS50F2V1B [15/31] Capacity tables

Daikin RKS60F2V1B [15/31] Capacity tables
Outdoor Units • R-410A • RKS-F2V1B
1
5
Split Sky Air • Outdoor Units
15
5 Capacity tables
5 - 1 Cooling capacity tables
FBQ50B8V1+RKS50F2V1B
Cooling 220-240V [50Hz]
Outdoor
Indoor
Outdoor temperature (°CDB)
EWB EDB 20 25 30 32 35 40
(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3TW25112-1B
SYMBOLS
AFR: Air flow rate (m
3
/min)
BF: Bypass factor
EWB: Entering wet bulb temp. (°CWB)
EDB: Entering dry bulb temp. (°CDB)
DB*: Dry bulb temp. (°CDB)
TC: Total capacity (kW)
SHC: Sensible heating capacity (kW)
PI: Power input (kW)
NOTES
1 Ratings shown are net capacities which include a deduction for
indoor fan motor heat
2 shows nominal (rated) capacities and power input.
3 SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
= 0.29 x 60 x AFR [m
3
/min.] x (1-BF) x (DB*-EDB)/860
Add SHC* to SHC if SHC > TC, then TC equal SHC
4 Direct interpolation is permissible.
Do not extrapolate.
5 Capacities are based on following conditions:
Corresponding refrigerant piping length: 7.5 m
Level difference: 0 m
6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.
Model
FBQ
35
AFR 11.5
BF 0.15
50
AFR 14
BF 0.15
60
AFR 19
BF 0.11