Troubleshooting Si12-710
118 Service Diagnosis
Troubleshooting
Check No.04
Refer to P.146
Check No.06
Refer to P.149
Check No. 04
Check the electronic expansion
valve.
(R7136)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
NO
NO
YES
NO
YES
NO
YES
YES
NO
Check No. 06
Check the outdoor unit heat
exchanger thermistor.
Check No. 06
Check the room temperature
thermistor.
Correct the wiring or piping
error.
Replace the defective Ev or
coil.
Replace the heat exchanger
thermistor.
Replace the room
temperature thermistor.
Replace the room
temperature thermistor or
indoor unit heat exchanger
thermistor.
Do the vacuum-drying.
Replace the indoor unit PCB.
Wiring or piping out of
spec?
Normal?
Error again?
Thermistor as
specified in its characteristic
chart?
Thermistor as
specified in its characteristic
chart?
Check the wiring and piping.
Change the gas to let moisture out
of the unit (after drawing a
vacuum).