EK 2 3 Min Joule integral and peak current values sustained by the circuit breaker are listed in Table 3 Table 3 Rated current In A ln 16 16 ln 32 32 ln 40 40 ln 63 63 ln 80 80 ln 100 Peak current Ip kA 1 15 2 05 2 70 3 90 4 80 5 60 Joule integral ft kA2s 1 45 5 0 9 70 28 0 40 0 82 0 2 4 Overall and installation dimensions are shown in Figures 1 and 2 figure 1 Overall and installation dimensions Figure 2 Overall and installation dimensions of two polar VDs of four polar VDs 2 5 Electric schematic diagrams of VD are shown in Figures 3 and 4 3 Complete Set 3 1 Delivery package includes VD1 63 1 pcs passport 1 pcs 4 Mounting 4 1 Mounting connection and putting VD into operation should be performed only by qualified electrical personnel 8