Daikin ATXN50MV16 [14/156] Electrical wiring connection

Содержание

ELECTRICAL WIRING CONNECTION IMPORTANT The figures shown in the table are for information purpose only They should be checked and selected to comply with the local national codes of regulations This is also subject to the type of installation and conductors used The appropriate voltage range should be checked with label data on the unit Inverter Power Indoor Model Indoor ATXN 20 25 35 50 60 Outdoor ARXN 20 25 35 50 60 Voltage range Power supply cable size 220 240VA 50HZ mnf Number of conductors Interconnection cable size 2 5 3 3 1 5 2 5 Number of conductors 4 4 Recommended fuse circuit breaker rating A 16 20 Inverter Power Outdoor All wires must be firmly connected Make sure all the wire do not touch the refrigerant pipings compressor or any moving parts The connecting wire between the indoor unit and the outdoor unit must be clamped by using provided cord anchorage The power supply cord must be equivalent to H07RN F which is the minimum requirement Make sure no external pressure is applied to the terminal connectors and wires Make sure all the covers are properly fixed to avoid any gap Use round crimp style terminal for connecting wires to the power supply terminal block Connect the wires by matching to the indication on terminal block Refer to the wiring diagram attached on the unit Used the correct screwdriver for terminal screws tightening Unsuitable screwdrivers can damage the screw head Over tightening can damage the terminal screws Do not connect wire of different gauge to same terminal Keep wiring in an orderly manner Prevent the wiring from obstructing other parts and the terminal box cover 1 12 mnf 1 5