8 Configuration
Installer reference guide
69
RRLQ004~008CA + RHBH/X04+08CB
ROTEX HPSU low temperature Bi‑bloc
4P384979-1B – 2016.02
decision to allow power interruption of the outdoor unit during
standstill depends on the ambient temperature, compressor
conditions and minimum internal timers.
To enable the power saving function setting, [E‑08] needs to be
enabled on the user interface in combination with the removal of the
power saving connector at the outdoor unit.
NOTICE
The power saving connector at the outdoor unit shall only
be removed when the main power supply to the application
is switched OFF.
In case of RRLQ004~008CAV3
1 2 3
# Code Description
N/A [E‑08] Power saving function for outdoor unit:
0: Disabled
1 (default): Enabled
In case of RRLQ011~016CAV3 and RRLQ011~016CAW1
Do NOT change the default setting.
# Code Description
N/A [E-08] Power saving function for outdoor unit:
0 (default): Disabled
1: Enabled
Power consumption control
Only applicable for RHBH/X04+08 + RHVH/X04+08. See
"5Application guidelines"on page10 for detailed information about
this functionality.
Pwr consumpt. control
# Code Description
[A.6.3.1] [4-08] Mode:
0 (No limitation)(default): Disabled.
1 (Continuous): Enabled: You can
set one power limitation value (in A
or kW) to which the system power
consumption will be limited for all the
time.
2 (Digital inputs): Enabled: You can
set up to four different power
limitation values (in A or kW) to
which the system power
consumption will be limited when the
corresponding digital input asks.
[A.6.3.2] [4-09] Type:
0 (Current): The limitation values are
set in A.
1 (Power)(default): The limitation
values are set in kW.
[A.6.3.3] [5-05] Value: Only applicable in case of full
time power limitation mode.
0A~50A, step: 1A (default: 50A)
[A.6.3.4] [5-09] Value: Only applicable in case of full
time power limitation mode.
0kW~20kW, step: 0.5kW (default:
20kW)
Amp. limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on current values.
[A.6.3.5.1] [5-05] Limit DI1
0A~50A, step: 1A (default: 50A)
[A.6.3.5.2] [5-06] Limit DI2
0A~50A, step: 1A (default: 50A)
[A.6.3.5.3] [5-07] Limit DI3
0A~50A, step: 1A (default: 50A)
[A.6.3.5.4] [5-08] Limit DI4
0A~50A, step: 1A (default: 50A)
kW limits for DI: Only applicable in case of power limitation mode
based on digital inputs and based on power values.
[A.6.3.6.1] [5-09] Limit DI1
0kW~20kW , step: 0.5kW (default:
20kW)
[A.6.3.6.2] [5-0A] Limit DI2
0kW~20kW, step: 0.5kW (default:
20kW)
[A.6.3.6.3] [5-0B] Limit DI3
0kW~20kW, step: 0.5kW (default:
20kW)
[A.6.3.6.4] [5-0C] Limit DI4
0kW~20kW, step: 0.5kW (default:
20kW)
Priority: Only applicable in case of an optional RKHW.