Tecnoclima BESST/R 31 [29/40] Enabling the so and sei controls

Tecnoclima SUPERBESST 41 [29/40] Enabling the so and sei controls
29
ENABLING THE “SO” AND “SEI” CONTROLS”
DO THE FOLLOWING FROM THE CONTROL PANEL:
The operations described below must be carried out with the maximum care so as not to affect the equipment regular operation.
In case of errors or interpretation doubts, please WAIT 15 SECONDS WITHOUST PRESSING ANY KEYS.
To enable the SO and SEI controls, act as follows:
Power on the unit, by turning ON the main system circuit breaker and the main equipment switch”. If this is the first startup, the OFF
indication appears on the display. In this case, press the
key to bring the machine back to stand-by. At this point, the return
temperature value appears on the display.
-
HOW TO SET THE“SO” (ON-OFF) REMOTE CONTROL):
- Now press the
and keys simultaneously to access the user parameters. The “Par” indication appears on the display,
indicating access to user parameters.
- Now press the
key to access the CF menu.
.
- The CF indication appears on the display, indicating the remote control parameter menu.
Pressing the
key CF19 is displayed: with the arrow key move to CF20, which indicates the “SO” parameter, that is ON-OFF To
set the remote SO control, just press
reduce the value from 0 to –13 (minus 13); then confirm with the key.
- Press the
key, , until the return water temperature value appears on the display.
- Power off the machine to store the value. - Power on again and check with the key
HOW TO SET THE“SEI” (SUMMER-WINTER CYCLE SWITCHING) REMOTE CONTROL
- Now press the
and keys simultaneously to access the user parameters. The Par indication appears on the display,
indicating access to user parameters.
- Now press the key to access the CF menu.
- The CF indication appears on the display, indicating the remote control parameter menu.
- Pressing the SET
key CF19 is displayed, which indicates the “SEI” parameter, that is remote summer/winter switching. To enable
the remote control, just press
and reduce the value from 0 to -14 (minus 14) with the arrow keys; then confirm with the key .
- Press the
key, until the return water temperature value appears on the display.
FILLING AND EMPTYING THE SYSTEM
FILLING
– Before starting to fill the system, turn OFF the main system
circuit breaker.
- Check if all the equipment and system drain cocks are closed
- Open all the equipment, system and respective terminals vent
valves