BY-PASS CALIBRATION OPERATIONS FOR 5-6-7-8 TYPES AND 13-14-15-16 TYPES
- - Switch on the appliance.
- Wait for the unit operation to get stabilized
- Check the heat rise between system delivery and return which must be between 4°C and 6°C
- If it is not so, operate the calibration by-pass, opening it to increase the heat rise or closing it to decrease the heat rise
- After adjusting the by-pass, bring the unit back to steady state and check if the heat rise between system delivery and return is between
4°C and 6°C.
- Replace the inspection panel
After operating the by-pass valve (to be installed downstream of the machine for 5-6-7-8 types and 13-14-15-16 types), wait for the
unit operation to get stabilized and repeat the check .
Should not it be possible to regulate the heat rise between system delivery and return within 4÷6°C, check the system load losses
and compare them with the flow rate-available lift chart of the pump on page 8.
A heat rise over 6°C entails the risk of ice forming in the plate heat exchanger
For the by-pass location, refer to the hydraulic diagram on page 21
It is not allowed to operate the unit with a heat rise over 6°C.
SWITCHING THE EQUIPMENT ON AND OFF
To SWITCH ON and OFF the “COOLING” and “HEATING” functions, use the CONTROL PANEL installed on the machine, or the two “SO”
ON-OFF and “SEI” SUMMER-WINTER REMOTE SWITCHES, if installed..
If the “Er 20” indication appears on the display in this first phase, please follow the instructions i:
- Check the water flow rate and the connection with the flow switch terminals 9 and 10.
To access the control panel, open the relevant door:
- Remove the lock screw
- Simultaneously press the (A) points and lift the door
After operating the control panel:
- Close the door and replace the lock screw.
Alarm icon
Mode (Heat, Cool…) Icon
Economy icon
(configurable)
Clock icon
Dysplayed quantity
measure unit
Resource (compressor, fans)icon
Menu navigation icon
Содержание
- Besst besst r series 1
- Conformity 2
- Warranty 2
- Installer 3
- Preparetion 3
- System manager 3
- Table of contents 3
- General directions 4
- Identification 4
- Tampering with the rating plate removing it or whatever else does not allow a sure identification of the product hinder tampering with the rating plate removing it or whatever else does not allow a sure identification of the product hinder any installation or maintenance interventions 4
- The unit can be identified through rating plate it bears the technical and performance data of the equipment should this plate be damaged or mislaid ask your local technical support service for a duplicate 4
- Fundamental safety rules 5
- Equipment description 6
- Besst besst r series 7
- Technical data weights 7
- Electric board and multifilar wiring diagram 9
- The units are provided with an electric board consisting of the following components 9
- Type 1 2 9 10 9
- Type 3 and 11 10
- Type 4 and 12 11
- Type 5 6 and 13 14 12
- Type 7 8 and 15 16 13
- Cooling circuit 14
- Accessories 15
- Below is a list of available accessories to be separately ordered accessory code 15
- Control panel 15
- Supporting resistor 15
- And down 17
- Fault indications 17
- Simultaneously press up 17
- Switching on and off 17
- To reset the alarms 17
- Cle cleaning 19
- Inactivity for a long period 19
- Maintenance 19
- Useful information 19
- D 480 540 580 670 mm 20
- Dimension type 1 2 9 10 3 4 11 12 5 6 13 14 7 8 15 16 20
- H 950 1150 1450 1650 mm 20
- Handling and transport 20
- L 1140 1340 1600 1990 mm 20
- Upon receiving the product 20
- Location 21
- Delivery to system 22
- Hydraulic connections 22
- Return from system 22
- Dimensions 23
- Dimensions type 1 2 9 10 3 4 11 12 5 6 13 14 7 8 15 16 23
- For weights refer to page 7 23
- Electrical connections 25
- Caution when sizing the power supply line for the besst r version the electric resistance value mentioned on page 7 technical data must also be considered together with the power value shown in the table above 26
- Power supply line sizing table for besst version only 26
- Remote alarm signal remote alarm signal 28
- Versione monofase versione trifase 28
- Enabling the so and sei controls 29
- Filling 29
- Filling and emptying the system 29
- Recommended working conditions 30
- Working limits 30
- First commissioning 31
- Preparation for first commissioning 31
- By pass calibration operations for 5 6 7 8 types and 13 14 15 16 types 32
- Switching the equipment on and off 32
- Checks during and after the first commissioning 35
- Defrosting control 35
- Inactivity for a long period 35
- Ordinary maintenance 35
- Compressor 36
- Control and display parameters 36
- Extraordinary maintenance 36
- Fault cause solution 38
- Troubleshooting 38
- Fault cause solution 39
Похожие устройства
- Tecnoclima BESST/R 31 Технические характеристики
- Tecnoclima BESST/R 31 Сертификат
- Tecnoclima BESST/R 31 Каталог
- Tecnoclima BESST/R 32 Инструкция по эксплуатации
- Tecnoclima BESST/R 32 Технические характеристики
- Tecnoclima BESST/R 32 Сертификат
- Tecnoclima BESST/R 32 Каталог
- Tecnoclima BESST/R 41 Инструкция по эксплуатации
- Tecnoclima BESST/R 41 Технические характеристики
- Tecnoclima BESST/R 41 Сертификат
- Tecnoclima BESST/R 41 Каталог
- Tecnoclima BESST/R 42 Инструкция по эксплуатации
- Tecnoclima BESST/R 42 Технические характеристики
- Tecnoclima BESST/R 42 Сертификат
- Tecnoclima BESST/R 42 Каталог
- Tecnoclima SUPERBESST 11 Инструкция по эксплуатации
- Tecnoclima SUPERBESST 11 Технические характеристики
- Tecnoclima SUPERBESST 11 Сертификат
- Tecnoclima SUPERBESST 11 Каталог
- Tecnoclima SUPERBESST 12 Инструкция по эксплуатации