EBHQ006+008BBV3
Unit for air to water heat pump system
4P347825-1A – 2013.04
Installation manual
11
10. PIPING CONNECTION WORK
10.1. Checking the water circuit
The units have a water inlet and water outlet for connection to a water
circuit. This circuit must be provided by a licensed technician and
must comply with all applicable legislations.
Before continuing the installation of the unit, beware of the following
points:
■ Two shut-off valves are delivered with the unit. To facilitate
service and maintenance, install one at the water inlet and one
at the water outlet of the unit.
■ Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit. Two drain valves are
provided inside the unit.
■ Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing. An automatic air purge is provided inside the outdoor
unit. Check that this air purge valve is not tightened too much so
that automatic release of air in the water circuit remains
possible.
■ Take care that the components installed in the field piping can
withstand the water pressure (maximum 3 bar + static pressure
of the pump).
■ The maximum waterpiping temperature is 65°C according to
safety device setting.
■ Always use materials which are compatible with the water used
in the system and with the materials used in the unit.
■ Select piping diameter in relation to required water flow and
available external static pressure (ESP) of the pump. The
recommended water piping diameter is 1".
■ The minimum required water flow for the unit operation is
12 l/min. When the water flow is lower than this minimum value,
flow error 7H will be displayed and the operation of the unit will
be stopped.
10.2. Checking the water volume and expansion vessel
pre-pressure
The unit is equipped with an expansion vessel of 6 litre which has a
default pre-pressure of 1 bar.
To assure proper operation of the unit, the pre-pressure of the
expansion vessel might need to be adjusted and the minimum and
maximum water volume must be checked.
1 Check that the total water volume in the installation, excluding
the internal water volume of the outdoor unit, is 10 l minimum.
Refer to "Technical specifications" on page 18 to know the
internal water volume of the outdoor unit.
The maximum allowed water volume is 250 l (if no glycol is
used). This is reduced to 175 l if 25% of propyleen glycol is
used.
In case no EKMBUHBA6V3 backup heater kit is installed, the
maximum allowed water volume is restricted to 150 l. In such
case we recommend the use of a thermostatic by-pass valve
(see example below).
As soon as the water circuit with the outdoor unit is in normal
operation range, this by-pass valve will gradually open, so the
entire circuit is than gradually heated.
Example
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Motorised thermostatic by-pass valve
8 Collector (field supply)
9 By-pass valve (field supply)
FHL1...3 Floor heating loop
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control the floor heating loop
(field supply)
2 Using the table below, determine if the expansion vessel
prepressure requires adjustment.
3 Using the table and instructions below, determine if the total
water volume in the installation is below the maximum allowed
water volume.
NOTICE
The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.
NOTICE
It is strongly recommended to install an additional filter on
the heating water circuit. Especially to remove metallic
particles from the field heating piping, it is advised to use a
magnetic or cyclone filter which can remove small
particles. Small particles can damage the unit and will not
be removed by the standard filter of the heat pump unit.
INFORMATION
In most applications this minimum water volume will have a
satisfying result.
In critical processes or in rooms with a high heat load
though, extra water volume might be required.
NOTICE
When circulation in each space heating loop is controlled
by remotely controlled valves, it is important that this
minimum water volume is kept even if all the valves are
closed. See example below.
Installation
height
difference
(a)
(a) Installation height difference: height difference (m) between the highest point of
the water circuit and the unit. If the unit is located at the highest point of the
installation, the installation height is considered 0 m.
Water volume
≤170 l
(with EKMBUH unit installed)
>170 l
(with EKMBUH unit installed)
≤150 l
(no EKMBUH unit installed)
≤7 m
No pre-pressure adjustment
required.
Actions required:
•pre-pressure must be
decreased, calculate
according to "Calculating the
pre-pressure of the
expansion vessel"
• check if the water volume is
lower than maximum allowed
water volume (use graph
below)
>7 m
Actions required:
•pre-pressure must be
increased, calculate
according to "Calculating the
pre-pressure of the
expansion vessel"
• check if the water volume is
lower than maximum allowed
water volume (use graph
below)
Expansion vessel of the unit
too small for the installation.
FHL1
FHL2
FHL3
M1
T1
M2
T2
M3
T3
M
9
645321
6
87
Содержание
- Installation manual 1
- Unit for air to water heat pump system 1
- Daikin europe n v 2
- Ebhq006bbv3 ekcbh008b v3 ebhq006bbv3 ekcbx008b v3 ebhq008bbv3 ekcbh008b v3 ebhq008bbv3 ekcbx008b v3 2
- En60335 2 40 2
- Jean pierre beuselinck director ostend 2nd of may 2013 2
- Low voltage 2006 95 ec electromagnetic compatibility 2004 108 ec 2
- P350991 1 2
- Installation manual 3
- Ontents 3
- Afety precautions 4
- Efinitions 4
- Meaning of used terms 4
- Meaning of warnings and symbols 4
- Combination and options 6
- Connection to a benefit kwh rate power supply 6
- General information 6
- Heating cooling units and heating only units 6
- Model identification 6
- Ntroduction 6
- Scope of the manual 6
- 2 3 5 4 7
- For access to the terminals following panels have to be removed as shown in the figure below 7
- Opening of the outdoor unit to gain access to the unit the service panels need to be opened as shown in the figure below 7
- Main components of the outdoor unit 8
- Electing an installation location 9
- Functional diagram of outdoor hydraulic compartment 9
- General precautions on outdoor installation location 9
- Main components of the outdoor unit switch box 9
- Place of installation 10
- Selecting an outdoor location in cold climates 10
- Wheater dependent precautions 10
- Dimensions of the outdoor unit 11
- Handling 11
- Handling and unpacking the unit 11
- Imensions and service space 11
- Inspection 11
- Nspectin 11
- Service space of the outdoor unit 11
- Ypical application examples 11
- Checking the water circuit 13
- Checking the water volume and expansion vessel pre pressure 13
- Iping connection work 13
- Connecting the water circuit 14
- Setting the pre pressure of the expansion vessel 14
- Protecting the water circuit against freezing 15
- Charging water 16
- Initial start up at low ambient temperatures 16
- Lectrical wiring work 16
- Mportant information regarding the refrigerant used 16
- Piping insulation 16
- Up and configuration 16
- Water piping freezing prevention 16
- Est run and final check 17
- Final check 17
- Pre run checks 17
- Procedure 17
- Test run operation manual 17
- Underfloor heating screed dry out program 17
- Aintenance and service 18
- Checks 18
- Maintenance activities 18
- Maintenance introduction 18
- Peration of the unit 18
- Service precautions 18
- General guidelines 19
- General symptoms 19
- Roubleshooting 19
- Service mode operation 19
- Electrical specifications 20
- Error codes 20
- Isposal requirements 20
- Nit specifications 20
- Technical specifications 20
Похожие устройства
- Foodatlas Постмикс LEF-4\5 Foodatlas Eco Инструкция по эксплуатации
- Foodatlas Постмикс LEF-4\5 Foodatlas Eco Сертификат
- Foodatlas Постмикс LEF-3\5 Foodatlas Eco Инструкция по эксплуатации
- Foodatlas Постмикс LEF-3\5 Foodatlas Eco Сертификат
- Foodatlas H001 Инструкция по эксплуатации
- Foodatlas H001 Сертификат
- Foodatlas PS-1 Инструкция по эксплуатации
- Foodatlas PS-1 Сертификат
- Foodatlas SM-1388 Инструкция по эксплуатации
- Foodatlas SM-1388 Сертификат
- Daikin EBLQ05C2V3 Руководство по монтажу
- Daikin EBLQ05C2V3 Общие правила техники безопасности
- Daikin EBLQ05C2V3 Руководство по применению для установщика
- Daikin EBLQ07C2V3 Руководство по монтажу
- Daikin EBLQ07C2V3 Руководство по применению для установщика
- Daikin EBLQ07C2V3 Общие правила техники безопасности
- Foodatlas KCB-1Y Инструкция по эксплуатации
- Foodatlas KCB-1Y Сертификат
- Foodatlas KCB-1F Инструкция по эксплуатации
- Foodatlas KCB-1F Сертификат