Daikin EBHQ008BBV3 [15/24] Protecting the water circuit against freezing
![Daikin EBHQ006BBV3 [15/24] Protecting the water circuit against freezing](/views2/1788338/page15/bgf.png)
EBHQ006+008BBV3
Unit for air to water heat pump system
4P347825-1A – 2013.04
Installation manual
13
10.5. Protecting the water circuit against freezing
Frost can damage the unit. As this unit is installed outdoors and thus
the hydraulic system is exposed to freezing temperatures, care must
be taken to prevent freezing of the system. All hydraulic parts are
insulated to reduce heat loss. Insulation must be foreseen on the field
piping.
The unit is already equipped with several features to prevent freezing.
■ The software contains special functions using pump and back
up heater (optionally) to protect the complete system against
freezing. This function will only be active when the unit is off.
However in case of power failure, above mentioned features can
not protect the unit from freezing.
If power failure can happen at times the unit is unattended,
Daikin recommends adding glycol to the water system. Refer to
Caution: "Corrosion of the system due to presence of glycol" on
page 13
Refer to "[4-04] Freeze protection function" in the EKCB
installation manual.
Depending on the expected lowest outdoor temperature, make
sure the water system is filled with a weight concentration of
glycol as mentioned in the table below.
Also refer to "Pre-run checks" on page 15.
NOTICE
■ The unit is only to be used in a closed water system.
Application in an open water circuit can lead to
excessive corrosion of the water piping.
■ Never use Zn-coated parts in the water circuit.
Excessive corrosion of these parts may occur as
copper piping is used in the unit's internal water
circuit.
■ When using a 3-way valve in the water circuit.
Preferably choose a ball type 3-way valve to
guarantee full separation between domestic hot water
and floor heating water circuit.
■ When using a 3-way valve or a 2-way valve in the
water circuit. The recommended maximum
changeover time of the valve should be less than 60
seconds.
Minimum outdoor
temperature
Glycol (a)(b)(c)
–5°C 10%
–10°C 15%
–15°C 20%
–20°C 25%
–25°C 30%
CAUTION
Units without backup heater kit installed are obligatory
always to use glycol.
WARNING
(a)
ETHYLENE GLYCOL IS TOXIC
(b)
The concentrations mentioned in the table
above will not prevent the medium from
freezing, but prevent the hydraulics from
bursting.
(c)
The maximum allowed water volume is then
reduced according to the figure "Checking the
maximum allowed water volume" on page 12
CAUTION
■ For installations with a domestic hot water tank,
the use of propylene glycol, including necessary
inhibitors, is only allowed if classified as
Category 3 according to EN1717 or the
applicable legislations.
■ In case of over-pressure when using glycol, be
sure to connect the safety valve to a drain pan in
order to recover the glycol.
Connecting a drain pipe is not required if no
glycol is used. The discharged water is then
drained via the bottom of the unit.
CAUTION
Corrosion of the system due to presence of glycol
Uninhibited glycol will turn acidic under the influence of
oxygen. This process is accelerated by presence of copper
and at higher temperatures. The acidic uninhibited glycol
attacks metal surfaces and forms galvanic corrosion cells
that cause severe damage to the system.
It is therefore of extreme importance:
■ that the water treatment is correctly executed by a
qualified water specialist;
■ that a glycol with corrosion inhibitors is selected to
counteract acids formed by the oxidation of glycols;
■ that in case of an installation with a domestic hot
water tank, only the use of propylene glycol, including
necessary inhibitors classified as Category 3
according to EN1717 or equivalent based on the
applicable legislations is allowed. In other installations
the use of ethylene glycol is permitted as well;
■ that no automotive glycol is used because their
corrosion inhibitors have a limited lifetime and contain
silicates which can foul or plug the system;
■ that galvanized piping is not used in glycol systems
since its presence may lead to the precipitation of
certain components in the glycolís corrosion inhibitor;
■ that it has to be made sure the glycol is compatible
with the used materials in the system.
NOTICE
Be aware of the hygroscopic property of glycol: it absorbs
moisture from its environment.
Leaving the cap off the glycol container causes the
concentration of water to increase. The glycol concen-
tration is then lower than assumed. And in consequence,
freezing can happen after all.
Preventive actions must be taken to ensure minimal
exposure of the glycol to air.
Содержание
- Installation manual 1
- Unit for air to water heat pump system 1
- Daikin europe n v 2
- Ebhq006bbv3 ekcbh008b v3 ebhq006bbv3 ekcbx008b v3 ebhq008bbv3 ekcbh008b v3 ebhq008bbv3 ekcbx008b v3 2
- En60335 2 40 2
- Jean pierre beuselinck director ostend 2nd of may 2013 2
- Low voltage 2006 95 ec electromagnetic compatibility 2004 108 ec 2
- P350991 1 2
- Installation manual 3
- Ontents 3
- Afety precautions 4
- Efinitions 4
- Meaning of used terms 4
- Meaning of warnings and symbols 4
- Combination and options 6
- Connection to a benefit kwh rate power supply 6
- General information 6
- Heating cooling units and heating only units 6
- Model identification 6
- Ntroduction 6
- Scope of the manual 6
- 2 3 5 4 7
- For access to the terminals following panels have to be removed as shown in the figure below 7
- Opening of the outdoor unit to gain access to the unit the service panels need to be opened as shown in the figure below 7
- Main components of the outdoor unit 8
- Electing an installation location 9
- Functional diagram of outdoor hydraulic compartment 9
- General precautions on outdoor installation location 9
- Main components of the outdoor unit switch box 9
- Place of installation 10
- Selecting an outdoor location in cold climates 10
- Wheater dependent precautions 10
- Dimensions of the outdoor unit 11
- Handling 11
- Handling and unpacking the unit 11
- Imensions and service space 11
- Inspection 11
- Nspectin 11
- Service space of the outdoor unit 11
- Ypical application examples 11
- Checking the water circuit 13
- Checking the water volume and expansion vessel pre pressure 13
- Iping connection work 13
- Connecting the water circuit 14
- Setting the pre pressure of the expansion vessel 14
- Protecting the water circuit against freezing 15
- Charging water 16
- Initial start up at low ambient temperatures 16
- Lectrical wiring work 16
- Mportant information regarding the refrigerant used 16
- Piping insulation 16
- Up and configuration 16
- Water piping freezing prevention 16
- Est run and final check 17
- Final check 17
- Pre run checks 17
- Procedure 17
- Test run operation manual 17
- Underfloor heating screed dry out program 17
- Aintenance and service 18
- Checks 18
- Maintenance activities 18
- Maintenance introduction 18
- Peration of the unit 18
- Service precautions 18
- General guidelines 19
- General symptoms 19
- Roubleshooting 19
- Service mode operation 19
- Electrical specifications 20
- Error codes 20
- Isposal requirements 20
- Nit specifications 20
- Technical specifications 20
Похожие устройства
- Foodatlas Постмикс LEF-4\5 Foodatlas Eco Инструкция по эксплуатации
- Foodatlas Постмикс LEF-4\5 Foodatlas Eco Сертификат
- Foodatlas Постмикс LEF-3\5 Foodatlas Eco Инструкция по эксплуатации
- Foodatlas Постмикс LEF-3\5 Foodatlas Eco Сертификат
- Foodatlas H001 Инструкция по эксплуатации
- Foodatlas H001 Сертификат
- Foodatlas PS-1 Инструкция по эксплуатации
- Foodatlas PS-1 Сертификат
- Foodatlas SM-1388 Инструкция по эксплуатации
- Foodatlas SM-1388 Сертификат
- Daikin EBLQ05C2V3 Руководство по монтажу
- Daikin EBLQ05C2V3 Общие правила техники безопасности
- Daikin EBLQ05C2V3 Руководство по применению для установщика
- Daikin EBLQ07C2V3 Руководство по монтажу
- Daikin EBLQ07C2V3 Руководство по применению для установщика
- Daikin EBLQ07C2V3 Общие правила техники безопасности
- Foodatlas KCB-1Y Инструкция по эксплуатации
- Foodatlas KCB-1Y Сертификат
- Foodatlas KCB-1F Инструкция по эксплуатации
- Foodatlas KCB-1F Сертификат