4 x Initial start-up
Daikin Control unit
RoCon mb
008.1446899_00 – 07/2019 – EN
Operating instructions
31
4 Initial start-up
In addition to the commissioning instructions listed in
this chapter, the specific commissioning instructions
listed in the respective installation instructions for the
Daikin Altherma M ECH
2
O must be observed.
The RoCon system offers a very wide range of application and
extension options.
The individual RoCon system components communicate via the
CAN data bus. For this reason, the RoCon BM1 printed circuit
boards and the RoCon B1 control panels of the Daikin
Altherma M ECH
2
O, as well as any optional EHS157034 room
station and EHS157068 mixer module system components are
connected to each other via data bus lines.
These system components must be allocated unique functional
IDs, so that the data exchange and the assignment within the
RoCon system functions without any problems.
In many applications, nothing needs to be changed in the basic
settings. The more RoCon system components that are inte-
grated in the RoCon system, the more adjustments that need to
be made during initial commissioning or when extending the
heating system.
The assignment of the functional IDs is easiest when carried out
via the "Setup Wizard" installation menu. Most IDs can also be
adapted subsequently to the conditions by means of individual
parameter settings in the specific parameter levels (see
Chapter 6).
a) If no optional RoCon system components are connected
to the Daikin Altherma M ECH
2
O, communication in the
RoCon system is limited to just the RoCon BM1 printed circuit
board and the integrated RoCon B1 control panel.
Adaptation of the IDs is not necessary.
The question displayed during initial commissioning "Use
Standard Config" can be confirmed by "Yes".
b) If optional RoCon system components such as
EHS157034 and / or EHS157068 are connected, adaptation
of the IDs may be necessary.
4.1 Fundamental aspects of the IDs and authorisations in the RoCon system
In the RoCon system, the following functional IDs that are rele-
vant for data exchange of the RoCon system components exist:
ID / Function System components Parameters Comments
Heating circuit ID
Unique numbering of a heating circuit
in the heating system in the RoCon
system. A maximum of 16 heating cir-
cuits can be controlled.
Daikin Altherma M ECH
2
O
(RoCon BM1)
[Unmixed Circ Config]
See tab. 6-14
Factory setting = 0
Should not normally be changed.
1)
EHS157034 room station [HC Assignment]
See tab. 6-1
Factory setting = Off
Adaptation required if there are different
heating circuits in the system and / or the
parameter [Master-RoCon] = On
EHS157068 mixer module [HC Assignment]
See tab. 6-15
Factory setting = Off
Must always be adapted to the setting of
the address switch (fig. 4-2).
Heat generator ID
Unique numbering of a heat genera-
tor in the RoCon system.
1)
Daikin Altherma M ECH
2
O
(RoCon BM1)
[BUS ID HS]
See tab. 6-14
Factory setting = 0
Should not normally be changed.
1)
EHS157068 mixer module [Boiler Assignment]
See tab. 6-15
Factory setting = 0
Should not normally be changed.
1)
Defines the heat generator that supplies
the assigned heating circuit with heat.
Terminal ID
Unique numbering of a RoCon B1 or
EHS157034 control unit from which a
heat generator and/or mixer module
can be remote controlled in the
RoCon system.
The authorisation for remote control
can be allocated to up to 10 control
units in the RoCon system. If remote
control in the RoCon system is to be
possible, the control unit must be
allocated the ID "0".
Daikin Altherma M ECH
2
O
(RoCon BM1)
[Terminaladress]
See tab. 6-1
Factory setting = Off
The value should be set to "0" if at least 1
mixer module is connected in the RoCon
system, and the mixer circuit is to be oper-
ated from the heat generator.
EHS157034 room station [Terminaladress]
See tab. 6-1 or
tab. 6-15 - depending
on the set heating cir-
cuit ID and the current
operating mode
Factory setting = Off
The value must be set to a unique numeri-
cal value in the RoCon system if the room
station system components are to be
remotely controlled using a valid device ID.