3 x Operation
FA ROTEX RoCon mb • 09/2017
13
In this operating mode, the ROTEX HPSU monobloc compact is
switched to Stand-by mode. The frost protection function (see
chap.
3.6.5) is maintained. In order to maintain this function, the
system may not be disconnected from the mains.
All controllers integrated in the RoCon system via the CAN bus
are primarily also switched to the "Standby" operating mode.
Operating mode Reducing
Reduced heating mode (lower target room temperature) ac-
cording to the target feed temperature set for reducing mode in
the parameter [T-Reduced] (see chap. 3.4.4).
Hot water preparation according to the set target hot water tem-
peratures and switching cycles in the hot water time program
[DHW Program 1] (see chap. 3.4.5).
Operating modes Heating, Cooling
Heating, cooling mode according to the target room temperature
set in the parameter [T-Room 1 Setpoint] (see chap. 3.4.3).
A connected outside temperature sensor (weather-dependent T-
HS control) or a connected room station also influence the target
feed temperature (prerequisite: parameter [HC Function] = On).
Hot water preparation according to the set target hot water tem-
peratures and switching cycles in the hot water time program
[DHW Program 1] (see chap.
3.4.5).
Operating mode Summer
Hot water preparation according to the set target hot water tem-
peratures and switching cycles in the hot water time program
[DHW Program 1] (see chap. 3.4.5).
All controllers integrated in the RoCon system via the CAN bus
are primarily also switched to the "Summer" operating mode.
Operating mode Automatic 1 (time program)
Automatic heating and setback mode according to the permanent
time programs (see chap.
3.4.7):
– [HC Program 1]
– [DHW Program 1]
Operating mode Automatic 2 (time program)
Automatic heating and setback mode according to the permanent
time programs (see chap. 3.4.7):
– [HC Program 2]
– [DHW Program 2]
Tab. 3-6 Resistance values for evaluating the EXT signal
Besides these operating modes, different temporary heating pro-
grams (see tab. 3-7) are available that are carried out with priority
after activation.
* only with technician code.
Tab. 3-7 Overview of temporary time programs
Fig. 3-8 Standard display in the "Standby" operating mode
(above the frost limit temperature)
If the hot water readiness is in setback mode in the
active operating mode, a temporary "DHW Re-
heating" can be set with the rotary switch setting
without having to change other standard settings (see
chap.
3.4.6).
Switching contact for external operating mode
switch-over
A potential-free switching contact connected via
ROTEX HPSU monobloc compact connection J8 at the "EXT"
terminals and wired with a resistor can also be used to switch
the operating mode from an external device (e.g. modem, …).
In this case, the switching contact functionality is dependent on
the parameter [Function BSC]:
– [Function BSC] = 0 (default setting): evaluation of the resist-
ance values (see tab. 3-6)
– [Function BSC] = 1: evaluation as a burner blocking contact.
If the switching contact is closed, the external heat generator
has priority.
Operating mode Resistance Tolerance
Standby < 680 Ω
± 5 %
Heating 1200 Ω
Reducing 1800 Ω
Summer 2700 Ω
Automatic 1 4700 Ω
Automatic 2 8200 Ω
The resistances specified in tab. 3-6 function in a toler-
ance field of 5%. Resistances outside this tolerance
field are interpreted as an open input. The heat gener
-
ator switches back to the previously active operating
mode.
The input is not considered for resistance values greater than
the value for "Automatic 2".
If several switching contacts are to be connected to the ROTEX
HPSU monobloc compact (e.g. Smart Grid, room thermostat),
the related functions may have a higher priority than external op
-
erating mode switch-over. The operating mode requested by the
EXT switching contact is then possibly not activated, or is only
activated later.
Temporary
time program
Setting/Activa-
tion in the level
Rotary switch
setting
Information
DHW Install DHW Install Chap. 3.4.6
Party
Time Program
Chap. 3.4.7
Away
Holiday
Vacation
Screed*
Configuration >
HC Configura-
tion
Chap. 3.6.13
If a temporary time program (DHW Install, Party, Away,
Holiday, Vacation, Screed) is started during the se-
lected operating mode, control is carried out primarily
according to the settings for this time program.
Содержание
355- Rotex control unit rocon mb rocon u1 rocon m1 operating instructions
- Rocon m1 mixer module 51
- Explanation of the parameter tables 40
- Refer to the manual 4
- Errors malfunctions and messages 55
- Recognising errors correcting malfunctions 55
- Commissioning rotex hpsu monobloc compact 33
- Warning signs and explanation of symbols 4
- Putting optional rocon system components into operation 33
- Basic functions and operating modes 10
- Use as intended 5
- Product description 6
- Avoiding danger 5
- Special system settings 21
- Parameter settings 40
- After first commissioning after successful basic configuration 37
- Special functions 20
- Safety 4
- Parameter overview 36
- Rotary switch setting time program 49
- Parameter levels for the rocon m1 mixer module 38
- Rotary switch setting set temp night 48
- Operation 7
- Rotary switch setting set temp day 48
- Operating support during 1st commissioning and during system extensions 32
- Rotary switch setting remote param 49
- Operating concept 9
- Rotary switch setting operating mode 48
- List of contents
- Rotary switch setting info 49 6 1 exit key special function 50 6 2 basic configuration parameter level 51 6 3 parameter levels of the
- Initial start up 31
- Rotary switch setting dhw set temp 48
- General 7
- Rotary switch setting dhw install 47
- Fundamental aspects of the ids and authorisations in the rocon system 31
- Rotary switch setting configuration 40
- For first commissioning or resetting to factory settings 36
- List of contents
- Glossary 7
- Notes 8
- List of keywords 3
- X safety
- Warning signs and explanation of symbols
- Safety
- Refer to the manual
- Meaning of the warnings
- X safety
- Validity
- Use as intended
- Order number
- Handling instructions
- Avoiding danger
- X product description
- Product description
- Danger
- X operation
- To clean the control unit use a dry cotton cloth using aggressive cleaning agents and other fluids can cause damage to devices or lead to an electric shock
- The displays and the keys of the control unit must be protected against the effects of moisture
- Operation
- Maximum energy exploitation
- If electrical components come into contact with water this can cause an electric shock as well as cause potentially fatal burns or injuries
- General
- Display and operating elements
- Display
- X operation
- Rotary switch
- Never operate the operating elements of the control unit with a hard pointed object this can cause damage and can cause the control to malfunction
- Explanation of symbols
- Controls
- Caution
- Exit key
- X operation
- Rotary button
- Operating concept
- X operation
- System information info
- Keylock
- Basic functions and operating modes
- Automatic defrost function
- X operation
- Displaying the operating data overview
- If the heating system is not drained the power supply must be ensured and the external main switch must remain switched on if there is a danger of frost
- Displaying the water pressure
- Caution
- Alternatively drain the heating system on the water side if there is a danger of frost
- Add glycol to the heating water circuit see installation and maintenance instructions
- A heating system that is not protected against frost can freeze in the event of frost and thus be damaged
- X operation
- Setting the operating mode
- Operating mode standby stand by
- X operation
- Operating modes heating cooling
- Operating mode summer
- Operating mode reducing
- Operating mode automatic 2 time program
- Operating mode automatic 1 time program
- X operation
- Unscheduled hot water preparation
- Temperature setting of setback mode
- Temperature setting of hot water generation
- Temperature setting of daytime room temperature
- Switching time program
- Setting
- X operation
- Permanent time programs
- X operation
- Temporary time programs
- X operation
- Terminal function
- System settings
- Setting the lcd display language date time
- X operation
- With outside temperatures below freezing there is a risk of material damage caused by frost
- Whisper mode
- Operation with glycol
- During active whisper mode the output in room heating and room cooling mode decreases such that it may no longer be possible to achieve pre set target temperature values
- Caution
- Activating deactivating whisper mode
- Activating deactivating terminal operation
- X operation
- Warning
- This storage tank charging is carried out even when standby operating mode is set
- There is a danger of scalding at target hot water temperatures over 60 c this is possible as the utility company evu is entitled to control current draw optimised according to supply and demand in the definitions for smart grid
- Smart grid sg
- Set 1 15 60 16
- Install scald protection in the hot water distri
- Ehs emergency operation
- Due to such forced charging the target hot water temperature in the hot water storage tank can exceed 60 c
- Bution line e g vta32 15 60 15 screw
- Activating deactivating emergency automatic operation
- X operation
- Way switching valves reference travel
- Special functions
- Manual operation
- 3 way switching valves reference travel
- X operation
- Special system settings
- Prior to initial commissioning of the floor heating system set the maximum temper ature limit in the rocon mb controller parameter t vbh1 max and the maximum permissible system temperature parameter max t flow
- In the event of malfunction or during manual operation the floor heating the screed or the floor structure could be damaged due to over heating
- If the floor heating is also used for room cooling the connection notes in the above point also apply to the connection of a moisture protection switch in the building
- Heat slope
- Expert
- Connect an overheating protection switch in the building at the ext plug connection to external operating mode switch over so that the rotex hpsu monobloc compact is switched to standby or summer operating mode see chap 3 with parameter room thermostat on or parameter interlink fct on the overheating protection switch must be connected so that the room thermostat s switching contact is interrupted
- Caution risk of overheating of floor heating
- Access rights technician code
- X operation
- Prior to initial commissioning and activation of cooling mode set the minimum temper ature limit to the minimum permissible system temperature in the rocon mb controller parameter min t flow cooling
- Manually adjusting the heat slope
- In the event of malfunction or incorrect parame ter settings the floor heating the screed or the floor structure could be damaged due to con densation
- Cooling slope
- Caution risk of condensation
- X operation
- With connected mixer module
- Weather dependent t hs control
- Frost protection function
- X operation
- Unsuitable feed temperatures can cause dam age to the floor heating system or dew formation on cooling surfaces
- Limit target feed temperatures to suitable temperature ranges
- Interlink function
- Design heat distribution areas with different design temperatures as hydraulically separate heating circuits if necessary design heating circuits with lim ited target feed temperatures as mixer cir cuits and regulate with a mixer module
- Caution
- Additional alternative heat generator
- X operation
- Special function switching contacts
- Heating support
- Air purge
- Anti legionella system
- X operation
- Warning
- There is a danger of scalding at target hot water temperatures over 60 c this is possible when using solar energy if the legionella protection or smart grid functions are activated or the target hot water temperature is set higher than 60 c
- Set 1 15 60 16
- Resetting to factory settings reset
- Option 2
- Option 1
- Install scald protection in the hot water distri
- Bution line e g vta32 15 60 15 screw
- X operation
- Screed program
- Option 3
- Function heating
- X operation
- Setting and starting the screed program
- Screed curing heating
- X operation
- Settings for optional circulation pump
- Relay test
- Defining the switching time program for the circulation pump
- X operation
- Remote control via internet
- X initial start up
- Initial start up
- Fundamental aspects of the ids and authorisations in the rocon system
- X initial start up
- Operating support during 1st commissioning and during system extensions
- For the rocon u1 room station
- For all rocon b1 and rocon u1 control units
- Mixer module rocon m1
- Commissioning rotex hpsu monobloc compact
- Assigning the terminal id on the rocon b1 control panel of the rotex hpsu monobloc compact
- X initial start up
- Putting optional rocon system components into operation
- X initial start up
- Sequence for initial commissioning see also chap 4
- Rocon u1 room station
- B configuration for mixing valve setting
- A configuration for the living room setting
- X initial start up
- Master rocon function
- Caretaker function
- Allocating the rocon m1 mixing module to a heat generator
- Allocating the rocon m1 mixing module to
- A heat generator
- Parameter overview
- For first commissioning or resetting to factory settings
- During initial commissioning after resetting to factory settings
- X parameter overview
- X parameter overview
- Rotary switch setting configuration
- Fa rotex rocon mb 09 2017 37
- After first commissioning after successful basic configuration
- Rotary switch setting remote param
- Rotary switch setting operating mode
- Rotary switch setting info
- Rotary switch setting dhw set temp
- Rotary switch setting dhw install
- Parameter levels for the rocon m1 mixer module
- Parameter levels for the rocon m1 mixer
- No function
- Module
- Fa rotex rocon mb 09 2017
- Exit key special function
- X parameter overview
- See chap 5
- Rotary switch setting time program
- Rotary switch setting set temp night
- Rotary switch setting set temp day
- X parameter overview
- Tab 5 12 parameters in the configuration rotary switch setting
- See chap 5
- Rotary switch setting time program
- Rotary switch setting remote param
- Rotary switch setting configuration
- Fa rotex rocon mb 09 2017 39
- Setup level
- Rotary switch setting configuration
- Parameter settings
- Explanation of the parameter tables
- X parameter settings
- X parameter settings
- Fa rotex rocon mb 09 2017 41
- X parameter settings
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 1 parameters in the configuration rotary switch setting setup level
- Fa rotex rocon mb 09 2017 43
- X parameter settings
- System configuration level
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 2 parameters in the configuration rotary switch setting system configuration level
- Hc configuration level
- Fa rotex rocon mb 09 2017 45
- Depending on the version individual information pa rameters are displayed that are not described in tab 6 2 for this see tab 6 12
- X parameter settings
- Fa rotex rocon mb 09 2017
- X parameter settings
- Rotary switch setting dhw install
- Fa rotex rocon mb 09 2017 47
- Dhw configuration level
- X parameter settings
- Tab 6 9 parameters in the dhw set temp rotary switch setting
- Tab 6 8 parameters in the set temp night rotary switch setting
- Tab 6 7 parameters in the set temp day rotary switch setting
- Tab 6 6 parameters in the operating mode rotary switch setting
- Rotary switch setting set temp night
- Rotary switch setting set temp day
- Rotary switch setting operating mode
- Rotary switch setting dhw set temp
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 11 parameters in the remote param rotary switch setting
- Tab 6 10 parameters in the time program rotary switch setting
- Rotary switch setting time program
- Rotary switch setting remote param
- Rotary switch setting info
- Fa rotex rocon mb 09 2017 49
- X parameter settings
- To enter press the exit button for at least 5 s
- Tab 6 13 parameters at the special level level
- Tab 6 12 parameters in the info rotary switch setting
- Fa rotex rocon mb 09 2017
- Exit key special function
- See chap 6
- Basic configuration parameter level
- Rotary switch setting time program
- An unlimited scope of available parameters exists at the indi vidual levels
- Rotary switch setting set temp night
- After the system config parameter has been set to inactive or delete in the configuration rotary switch setting
- Rotary switch setting set temp day
- Rotary switch setting remote param
- Rotary switch setting operating mode
- Rotary switch setting info
- Rotary switch setting dhw set temp
- Rotary switch setting dhw install
- Rotary switch setting configuration
- Parameter levels of the rocon m1 mixer module
- X parameter settings
- Only the corresponding sections are referred to below signif icant differences are explained in more detail
- This parameter level only appears during initial commissioning if the answer selected for the use standard config prompt was no or
- On setting a rocon u1 room station assigned to the mixer module via the heating circuit id to living room the parameter t room adj is available the target room temperature can be changed in the range 5 k to 5 k with the rotary button this function is not available if the rocon u1 is used as a remote control in terminal function
- The parameter levels parameter meanings setting ranges and connected functions are basically described in the same way as in the previous sections
- On setting a control panel to mix valve x terminal function the displayed values refer to the components pump mix valve connected to the rocon m1 of the mixer circuit assigned via the device id
- Setup level
- No function
- See chap 6 3 and 6 3
- See chap 6 0
- Fa rotex rocon mb 09 2017 51
- X parameter settings
- Tab 6 15 parameters in the configuration rotary switch setting setup level
- Rotary switch setting configuration setup level
- Fa rotex rocon mb 09 2017
- X parameter settings
- Rotary switch setting configuration mixer config level
- Fa rotex rocon mb 09 2017 53
- X parameter settings
- Tab 6 16 parameters in the configuration rotary switch setting mixer config level
- Fa rotex rocon mb 09 2017
- X errors malfunctions and messages
- Troubleshooting
- Secure potential equalisation before touching electronic parts e g by touching an earthed metallic part
- Recognising errors correcting malfunctions
- Reading out the protocol
- Errors malfunctions and messages
- Electrostatic charges can lead to voltage arcing that can destroy the electronic components
- Current error display
- Caution
- X errors malfunctions and messages
- Malfunctions and fault codes
- Emergency operation
- Ehs emergency operation
- X glossary
- Glossary
- Switching time program
- X notes
- User specific settings
- X notes
- Rocon device id comments
- Parameters
- Ids in the rocon can bus system
- Fa rotex rocon mb 09 2017 59
- Enter the parameter changes you have made in the following table and in the rotex hpsu monobloc compact operating manual
- Circulation time
- Other items
- X list of keywords
- List of keywords
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Изучите различные режимы работы систем отопления и горячего водоснабжения, включая автоматические и временные программы для оптимизации комфорта и эффективности.