Screed curing heating
The drying process for the screed cannot be exactly predicted. If
there is a high degree of humidity, sometimes it can stop com-
pletely. The drying process can be speeded up by activating the
floor heating (screed curing heating) or measures such as me
-
chanical drying.
Each screed curing heating must be ordered separately by the
client as an extra service in accordance with German con-
struction contract procedures (VOB). The workability of the
screed is a prerequisite for beginning the work of the top floor in-
staller, so that he can produce defect free work.
With standard settings, the combined function and screed curing
heating program can be activated to achieve the required re-
sidual moisture in the screed for screed curing (see fig. 3-19).
However, the residual moisture of the screed must basically be
checked metrologically before the flooring can be laid.
More detailed explanations and possible setting values for this function can be
found in chapters
6.2.3 and 6.13.2.
Setting and starting the screed program
The screed program already includes factory default values
which can, however, be individually adjusted.
The day on which the screed program is activated is not counted
in the runtime of the program. The 1st day starts at the change of
day at 00:00 am. On the day of activation, the setting of the 1st
program day is used for heating for the remaining time.
● Enter the technician code (see chap. 3.6.1).
After entering, the "Setup" level is displayed.
● Use the rotary button to select the parameters [Interlink fct]
and [Room thermostat] and check whether they are deacti-
vated (see tab. 6-1).
Both parameters must be set to "Off" before starting the
screed program.
● Briefly press the Exit button.
An overview is displayed.
● Use the rotary button to select the "HC Configuration" level.
An overview is displayed.
● Use the rotary button to select the [Screed Program]
parameter.
● Check the settings for the screed program, and set according
to the manufacturer specifications for the screed if necessary
(see fig. 3-20).
– The adjustment range always lies between 0.0 and 65 °C.
– The increment is 1 °C.
Tab. 3-11 Screed program default settings
● Briefly press the Exit button.
An overview is displayed.
● Use the rotary button to select the [Screed] parameter.
● Confirm the selection with a brief push of the rotary button.
The setting of the parameter is displayed.
● Use the rotary button to set the parameter for the function to
"On", and confirm by pressing the rotary button briefly (see
fig. 3-20).
Screed program starts.
The key lock (if it was activated prior to the start of this
function) is reactivated within 2 s to prevent undesired
cancellation of the function through operation of the
RoCon
mb controller.
After the screed program has ended, the RoCon mb control unit
continues to work in the previously set operating mode. If not con-
figured beforehand, the following finishing work is necessary.
a) On connection without room station:
● Set the heating characteristic curve or desired target feed
temperature.
b) On connection with room station:
● Activate the room station.
● Set the heating characteristic curve or desired target feed
temperature.If necessary, activate the parameter [Room
Influence] and set the target room temperature.
t
1
Start temperature 25 °C (38 °C with system 70)
t
2
Maximum heating circuit temperature
t
V
T-HS
Z Duration of the screed function in days after starting the function
Fig. 3-18 Chronological sequence of the screed program during the
function heating
Fig. 3-19 Chronological sequence of the screed program during the
combined function and screed curing heating (for legend, see
fig. 3-18)
Day Factory setting Day Factory setting
1 - 3 25 °C 10 - 19 55 °C
4 - 7 55 °C 20 40 °C
8 25 °C 21 25 °C
9 40 °C 22 - 26 -
Содержание
355- Rotex control unit rocon mb rocon u1 rocon m1 operating instructions
- Rocon m1 mixer module 51
- Explanation of the parameter tables 40
- Refer to the manual 4
- Errors malfunctions and messages 55
- Recognising errors correcting malfunctions 55
- Commissioning rotex hpsu monobloc compact 33
- Warning signs and explanation of symbols 4
- Putting optional rocon system components into operation 33
- Basic functions and operating modes 10
- Use as intended 5
- Product description 6
- Avoiding danger 5
- Special system settings 21
- Parameter settings 40
- After first commissioning after successful basic configuration 37
- Special functions 20
- Safety 4
- Parameter overview 36
- Rotary switch setting time program 49
- Parameter levels for the rocon m1 mixer module 38
- Rotary switch setting set temp night 48
- Operation 7
- Rotary switch setting set temp day 48
- Operating support during 1st commissioning and during system extensions 32
- Rotary switch setting remote param 49
- Operating concept 9
- Rotary switch setting operating mode 48
- List of contents
- Rotary switch setting info 49 6 1 exit key special function 50 6 2 basic configuration parameter level 51 6 3 parameter levels of the
- Initial start up 31
- Rotary switch setting dhw set temp 48
- General 7
- Rotary switch setting dhw install 47
- Fundamental aspects of the ids and authorisations in the rocon system 31
- Rotary switch setting configuration 40
- For first commissioning or resetting to factory settings 36
- List of contents
- Glossary 7
- Notes 8
- List of keywords 3
- X safety
- Warning signs and explanation of symbols
- Safety
- Refer to the manual
- Meaning of the warnings
- X safety
- Validity
- Use as intended
- Order number
- Handling instructions
- Avoiding danger
- X product description
- Product description
- Danger
- X operation
- To clean the control unit use a dry cotton cloth using aggressive cleaning agents and other fluids can cause damage to devices or lead to an electric shock
- The displays and the keys of the control unit must be protected against the effects of moisture
- Operation
- Maximum energy exploitation
- If electrical components come into contact with water this can cause an electric shock as well as cause potentially fatal burns or injuries
- General
- Display and operating elements
- Display
- X operation
- Rotary switch
- Never operate the operating elements of the control unit with a hard pointed object this can cause damage and can cause the control to malfunction
- Explanation of symbols
- Controls
- Caution
- Exit key
- X operation
- Rotary button
- Operating concept
- X operation
- System information info
- Keylock
- Basic functions and operating modes
- Automatic defrost function
- X operation
- Displaying the operating data overview
- If the heating system is not drained the power supply must be ensured and the external main switch must remain switched on if there is a danger of frost
- Displaying the water pressure
- Caution
- Alternatively drain the heating system on the water side if there is a danger of frost
- Add glycol to the heating water circuit see installation and maintenance instructions
- A heating system that is not protected against frost can freeze in the event of frost and thus be damaged
- X operation
- Setting the operating mode
- Operating mode standby stand by
- X operation
- Operating modes heating cooling
- Operating mode summer
- Operating mode reducing
- Operating mode automatic 2 time program
- Operating mode automatic 1 time program
- X operation
- Unscheduled hot water preparation
- Temperature setting of setback mode
- Temperature setting of hot water generation
- Temperature setting of daytime room temperature
- Switching time program
- Setting
- X operation
- Permanent time programs
- X operation
- Temporary time programs
- X operation
- Terminal function
- System settings
- Setting the lcd display language date time
- X operation
- With outside temperatures below freezing there is a risk of material damage caused by frost
- Whisper mode
- Operation with glycol
- During active whisper mode the output in room heating and room cooling mode decreases such that it may no longer be possible to achieve pre set target temperature values
- Caution
- Activating deactivating whisper mode
- Activating deactivating terminal operation
- X operation
- Warning
- This storage tank charging is carried out even when standby operating mode is set
- There is a danger of scalding at target hot water temperatures over 60 c this is possible as the utility company evu is entitled to control current draw optimised according to supply and demand in the definitions for smart grid
- Smart grid sg
- Set 1 15 60 16
- Install scald protection in the hot water distri
- Ehs emergency operation
- Due to such forced charging the target hot water temperature in the hot water storage tank can exceed 60 c
- Bution line e g vta32 15 60 15 screw
- Activating deactivating emergency automatic operation
- X operation
- Way switching valves reference travel
- Special functions
- Manual operation
- 3 way switching valves reference travel
- X operation
- Special system settings
- Prior to initial commissioning of the floor heating system set the maximum temper ature limit in the rocon mb controller parameter t vbh1 max and the maximum permissible system temperature parameter max t flow
- In the event of malfunction or during manual operation the floor heating the screed or the floor structure could be damaged due to over heating
- If the floor heating is also used for room cooling the connection notes in the above point also apply to the connection of a moisture protection switch in the building
- Heat slope
- Expert
- Connect an overheating protection switch in the building at the ext plug connection to external operating mode switch over so that the rotex hpsu monobloc compact is switched to standby or summer operating mode see chap 3 with parameter room thermostat on or parameter interlink fct on the overheating protection switch must be connected so that the room thermostat s switching contact is interrupted
- Caution risk of overheating of floor heating
- Access rights technician code
- X operation
- Prior to initial commissioning and activation of cooling mode set the minimum temper ature limit to the minimum permissible system temperature in the rocon mb controller parameter min t flow cooling
- Manually adjusting the heat slope
- In the event of malfunction or incorrect parame ter settings the floor heating the screed or the floor structure could be damaged due to con densation
- Cooling slope
- Caution risk of condensation
- X operation
- With connected mixer module
- Weather dependent t hs control
- Frost protection function
- X operation
- Unsuitable feed temperatures can cause dam age to the floor heating system or dew formation on cooling surfaces
- Limit target feed temperatures to suitable temperature ranges
- Interlink function
- Design heat distribution areas with different design temperatures as hydraulically separate heating circuits if necessary design heating circuits with lim ited target feed temperatures as mixer cir cuits and regulate with a mixer module
- Caution
- Additional alternative heat generator
- X operation
- Special function switching contacts
- Heating support
- Air purge
- Anti legionella system
- X operation
- Warning
- There is a danger of scalding at target hot water temperatures over 60 c this is possible when using solar energy if the legionella protection or smart grid functions are activated or the target hot water temperature is set higher than 60 c
- Set 1 15 60 16
- Resetting to factory settings reset
- Option 2
- Option 1
- Install scald protection in the hot water distri
- Bution line e g vta32 15 60 15 screw
- X operation
- Screed program
- Option 3
- Function heating
- X operation
- Setting and starting the screed program
- Screed curing heating
- X operation
- Settings for optional circulation pump
- Relay test
- Defining the switching time program for the circulation pump
- X operation
- Remote control via internet
- X initial start up
- Initial start up
- Fundamental aspects of the ids and authorisations in the rocon system
- X initial start up
- Operating support during 1st commissioning and during system extensions
- For the rocon u1 room station
- For all rocon b1 and rocon u1 control units
- Mixer module rocon m1
- Commissioning rotex hpsu monobloc compact
- Assigning the terminal id on the rocon b1 control panel of the rotex hpsu monobloc compact
- X initial start up
- Putting optional rocon system components into operation
- X initial start up
- Sequence for initial commissioning see also chap 4
- Rocon u1 room station
- B configuration for mixing valve setting
- A configuration for the living room setting
- X initial start up
- Master rocon function
- Caretaker function
- Allocating the rocon m1 mixing module to a heat generator
- Allocating the rocon m1 mixing module to
- A heat generator
- Parameter overview
- For first commissioning or resetting to factory settings
- During initial commissioning after resetting to factory settings
- X parameter overview
- X parameter overview
- Rotary switch setting configuration
- Fa rotex rocon mb 09 2017 37
- After first commissioning after successful basic configuration
- Rotary switch setting remote param
- Rotary switch setting operating mode
- Rotary switch setting info
- Rotary switch setting dhw set temp
- Rotary switch setting dhw install
- Parameter levels for the rocon m1 mixer module
- Parameter levels for the rocon m1 mixer
- No function
- Module
- Fa rotex rocon mb 09 2017
- Exit key special function
- X parameter overview
- See chap 5
- Rotary switch setting time program
- Rotary switch setting set temp night
- Rotary switch setting set temp day
- X parameter overview
- Tab 5 12 parameters in the configuration rotary switch setting
- See chap 5
- Rotary switch setting time program
- Rotary switch setting remote param
- Rotary switch setting configuration
- Fa rotex rocon mb 09 2017 39
- Setup level
- Rotary switch setting configuration
- Parameter settings
- Explanation of the parameter tables
- X parameter settings
- X parameter settings
- Fa rotex rocon mb 09 2017 41
- X parameter settings
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 1 parameters in the configuration rotary switch setting setup level
- Fa rotex rocon mb 09 2017 43
- X parameter settings
- System configuration level
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 2 parameters in the configuration rotary switch setting system configuration level
- Hc configuration level
- Fa rotex rocon mb 09 2017 45
- Depending on the version individual information pa rameters are displayed that are not described in tab 6 2 for this see tab 6 12
- X parameter settings
- Fa rotex rocon mb 09 2017
- X parameter settings
- Rotary switch setting dhw install
- Fa rotex rocon mb 09 2017 47
- Dhw configuration level
- X parameter settings
- Tab 6 9 parameters in the dhw set temp rotary switch setting
- Tab 6 8 parameters in the set temp night rotary switch setting
- Tab 6 7 parameters in the set temp day rotary switch setting
- Tab 6 6 parameters in the operating mode rotary switch setting
- Rotary switch setting set temp night
- Rotary switch setting set temp day
- Rotary switch setting operating mode
- Rotary switch setting dhw set temp
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 11 parameters in the remote param rotary switch setting
- Tab 6 10 parameters in the time program rotary switch setting
- Rotary switch setting time program
- Rotary switch setting remote param
- Rotary switch setting info
- Fa rotex rocon mb 09 2017 49
- X parameter settings
- To enter press the exit button for at least 5 s
- Tab 6 13 parameters at the special level level
- Tab 6 12 parameters in the info rotary switch setting
- Fa rotex rocon mb 09 2017
- Exit key special function
- See chap 6
- Basic configuration parameter level
- Rotary switch setting time program
- An unlimited scope of available parameters exists at the indi vidual levels
- Rotary switch setting set temp night
- After the system config parameter has been set to inactive or delete in the configuration rotary switch setting
- Rotary switch setting set temp day
- Rotary switch setting remote param
- Rotary switch setting operating mode
- Rotary switch setting info
- Rotary switch setting dhw set temp
- Rotary switch setting dhw install
- Rotary switch setting configuration
- Parameter levels of the rocon m1 mixer module
- X parameter settings
- Only the corresponding sections are referred to below signif icant differences are explained in more detail
- This parameter level only appears during initial commissioning if the answer selected for the use standard config prompt was no or
- On setting a rocon u1 room station assigned to the mixer module via the heating circuit id to living room the parameter t room adj is available the target room temperature can be changed in the range 5 k to 5 k with the rotary button this function is not available if the rocon u1 is used as a remote control in terminal function
- The parameter levels parameter meanings setting ranges and connected functions are basically described in the same way as in the previous sections
- On setting a control panel to mix valve x terminal function the displayed values refer to the components pump mix valve connected to the rocon m1 of the mixer circuit assigned via the device id
- Setup level
- No function
- See chap 6 3 and 6 3
- See chap 6 0
- Fa rotex rocon mb 09 2017 51
- X parameter settings
- Tab 6 15 parameters in the configuration rotary switch setting setup level
- Rotary switch setting configuration setup level
- Fa rotex rocon mb 09 2017
- X parameter settings
- Rotary switch setting configuration mixer config level
- Fa rotex rocon mb 09 2017 53
- X parameter settings
- Tab 6 16 parameters in the configuration rotary switch setting mixer config level
- Fa rotex rocon mb 09 2017
- X errors malfunctions and messages
- Troubleshooting
- Secure potential equalisation before touching electronic parts e g by touching an earthed metallic part
- Recognising errors correcting malfunctions
- Reading out the protocol
- Errors malfunctions and messages
- Electrostatic charges can lead to voltage arcing that can destroy the electronic components
- Current error display
- Caution
- X errors malfunctions and messages
- Malfunctions and fault codes
- Emergency operation
- Ehs emergency operation
- X glossary
- Glossary
- Switching time program
- X notes
- User specific settings
- X notes
- Rocon device id comments
- Parameters
- Ids in the rocon can bus system
- Fa rotex rocon mb 09 2017 59
- Enter the parameter changes you have made in the following table and in the rotex hpsu monobloc compact operating manual
- Circulation time
- Other items
- X list of keywords
- List of keywords
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Узнайте, как ускорить процесс высыхания стяжки с помощью обогрева и механической сушки. Подробные инструкции по настройке и запуску программы стяжки.