Daikin RKHW16MXB500C — настройка параметров системы для электрического обогрева [44/64]
Превью страниц
Страница 44 /
64
![Daikin RKHW16MXB500C [44/64] System configuration level](/views2/1788403/page44/bg2c.png)
44
FA ROTEX RoCon mb • 09/2017
6 x Parameter settings
6.2.2 "System Configuration" level
Parameters Description Access Setting range
Min / Max
Factory
setting
Incre-
ment
BE HF
Power DHW Heat output of the electric heater booster for hot water preparation N E 1000 -
40,000
W
3000 W 1000 W
BUH s1 power Heat output of the electric heater booster for heating support stage 1
See operating instructions for heating element BUxx.
N E - - -
BUH s2 power Heat output of the electric heater booster for heating support stage 2
See operating instructions for heating element BUxx.
N E - - -
Power BIV Setting limits the heating support output. N E 3000 -
40000
W
15000 W 1000 W
TDiff-DHW CH Sup-
port
Only if parameter [HZU] = On.
Heating support is activated if
Tdhw > T
HZUmin
+ 4 K and Tdhw > [T-HS Setpoint] + 1 K.
Heating support is deactivated if
Tdhw < T
HZUmin
or Tdhw < [T-HS Setpoint].
T
HZUmin
= currently active target hot water temperature [T-DHW Setpoint] + set parameter val-
ue [TDiff-DHW CH Support].
Tdhw = current hot water storage tank temperature
[T-HS Setpoint] = currently active target feed temperature (see tab. 6-12 and chap. 3.6.4)
N E 2 - 15 5 1
T vbh1 max Setting limits the target feed temperature (measured against t
V, BH
) when the heating support
function is active.
N E 5 - 85 °C 60 °C 1 °C
Equilibrium Temp Setting influences the effect of the potential-free AUX switching contact (toggle switch output
A) defined in the parameter [AUX Fct].
Only if parameter [Equilibrium Func.] = On:
Outside temperature as of which the optional heater booster is activated to support room heat-
ing. The bi-valence temperature is relevant to operation of the optional heater booster due to
a backup requirement (room heating mode). The temperature of the temperature sensor (info
value TA) integrated in the heat pump outdoor unit is used for this.
E E -15 to +35 °C 0 °C 1 °C
Function BSC Selection of the functionality of switching contact EXT (J8):
0: evaluation of the resistance valves (see chap. 3.4.2)
1: evaluation as a burner blocking contact. If the switching contact is closed, the external heat
generator has priority.
S E 0 - 1 0 -
Quite Mode Mode for low-noise operation at reduced output (see chap. 3.4.11).
0: deactivated
1: activated
2: only operated in whisper mode at night from 22:00 to 06:00 hours.
E E 0 - 2 0 -
Quiet level On selection of low-noise operation, three noise levels can be set.
0: less quiet. The output can decline in colder ambient conditions.
1: medium quiet. Reduced output is possible under all conditions.
2: quietest. The output is reduced under all conditions.
S E 0 - 2 0 -
AUX Fct Setting assigns the switching conditions for the potential-free AUX switching contact (toggle
switch output A, see chap.
3.6.9).
0: function deactivated
AUX switching contact switches;
1: if storage tank temperature (Tdhw) ≥ value of parameter [T-DHW 1 min].
2: if a cooling request or heating request is present.
3: if a hot water request to the backup heater (BUxx) is present or the configured backup heater
is requested for heating support.
4: if an error is pending.
5: if the sensor value (TVBH) is > 60 °C.
6: if the outside temperature is < parameter value [Equilibrium Temp].
→ Heat pump continues to operate = parallel bi-valence mode.
7: if the outside temperature is < parameter value [Equilibrium Temp] + a heating request or a
hot water request is present.
→ Heat pump does not continue to operate = alternative bi-valence mode.
8: if a hot water request is present.
9: if the outside temperature is < parameter value [Equilibrium Temp] + heat request "room
heating" (not for hot water request). Heat pump no longer operates in room heating mode be
-
low the value set in the parameter [Equilibrium Temp] - only in hot water mode.
Application: alternative room heating bi-valence mode if the boiler is hydraulically integrated so
that it directly heats the unpressurised storage tank water of the ROTEX HPSU monobloc com
-
pact (connection via solar connections).
10: "multi-oil" - if the outside temperature is < parameter value [Equilibrium Temp] + heat re-
quest "room heating" (not for hot water request). Heat pump no longer operates in room heat-
ing mode below the value set in the parameter [Equilibrium Temp] - only in hot water mode.
Application: alternative room heating bi-valence mode if the boiler is hydraulically integrated in
the heat pump feed. For this application type, the frost protection function must be deactivated
on the ROTEX HPSU monobloc compact (parameter [T-Frost Protect] = Off).
11: if the heat pump is in "Cooling" operating mode.
N E 0 - 9 0 1
AUX time AUX switching contact (A) only switches after a delay if the switching condition (see parameter
[AUX Fct]) is present for longer than the set time.
N E 0 - 600 s 120 s 5 s
T-DHW 1 min Storage tank temperature (Tdhw) switching threshold for AUX switching contact (see parame-
ter [AUX Fct]).
N E 20 - 85 °C 50 °C 1 °C
Delta-T CH Target spread for room heating. The heating circulation pump of the ROTEX HPSU monobloc
compact regulates the flow rate to achieve the target spread stored in the parameter between
the target feed temperature and return temperature (t
V, BH
- t
R1
).
N E 2 - 20 K 7 K 1 K
Содержание
355- Rotex control unit rocon mb rocon u1 rocon m1 operating instructions
- Rocon m1 mixer module 51
- Explanation of the parameter tables 40
- Refer to the manual 4
- Errors malfunctions and messages 55
- Recognising errors correcting malfunctions 55
- Commissioning rotex hpsu monobloc compact 33
- Warning signs and explanation of symbols 4
- Putting optional rocon system components into operation 33
- Basic functions and operating modes 10
- Use as intended 5
- Product description 6
- Avoiding danger 5
- Special system settings 21
- Parameter settings 40
- After first commissioning after successful basic configuration 37
- Special functions 20
- Safety 4
- Parameter overview 36
- Rotary switch setting time program 49
- Parameter levels for the rocon m1 mixer module 38
- Rotary switch setting set temp night 48
- Operation 7
- Rotary switch setting set temp day 48
- Operating support during 1st commissioning and during system extensions 32
- Rotary switch setting remote param 49
- Operating concept 9
- Rotary switch setting operating mode 48
- List of contents
- Rotary switch setting info 49 6 1 exit key special function 50 6 2 basic configuration parameter level 51 6 3 parameter levels of the
- Initial start up 31
- Rotary switch setting dhw set temp 48
- General 7
- Rotary switch setting dhw install 47
- Fundamental aspects of the ids and authorisations in the rocon system 31
- Rotary switch setting configuration 40
- For first commissioning or resetting to factory settings 36
- List of contents
- Glossary 7
- Notes 8
- List of keywords 3
- X safety
- Warning signs and explanation of symbols
- Safety
- Refer to the manual
- Meaning of the warnings
- X safety
- Validity
- Use as intended
- Order number
- Handling instructions
- Avoiding danger
- X product description
- Product description
- Danger
- X operation
- To clean the control unit use a dry cotton cloth using aggressive cleaning agents and other fluids can cause damage to devices or lead to an electric shock
- The displays and the keys of the control unit must be protected against the effects of moisture
- Operation
- Maximum energy exploitation
- If electrical components come into contact with water this can cause an electric shock as well as cause potentially fatal burns or injuries
- General
- Display and operating elements
- Display
- X operation
- Rotary switch
- Never operate the operating elements of the control unit with a hard pointed object this can cause damage and can cause the control to malfunction
- Explanation of symbols
- Controls
- Caution
- Exit key
- X operation
- Rotary button
- Operating concept
- X operation
- System information info
- Keylock
- Basic functions and operating modes
- Automatic defrost function
- X operation
- Displaying the operating data overview
- If the heating system is not drained the power supply must be ensured and the external main switch must remain switched on if there is a danger of frost
- Displaying the water pressure
- Caution
- Alternatively drain the heating system on the water side if there is a danger of frost
- Add glycol to the heating water circuit see installation and maintenance instructions
- A heating system that is not protected against frost can freeze in the event of frost and thus be damaged
- X operation
- Setting the operating mode
- Operating mode standby stand by
- X operation
- Operating modes heating cooling
- Operating mode summer
- Operating mode reducing
- Operating mode automatic 2 time program
- Operating mode automatic 1 time program
- X operation
- Unscheduled hot water preparation
- Temperature setting of setback mode
- Temperature setting of hot water generation
- Temperature setting of daytime room temperature
- Switching time program
- Setting
- X operation
- Permanent time programs
- X operation
- Temporary time programs
- X operation
- Terminal function
- System settings
- Setting the lcd display language date time
- X operation
- With outside temperatures below freezing there is a risk of material damage caused by frost
- Whisper mode
- Operation with glycol
- During active whisper mode the output in room heating and room cooling mode decreases such that it may no longer be possible to achieve pre set target temperature values
- Caution
- Activating deactivating whisper mode
- Activating deactivating terminal operation
- X operation
- Warning
- This storage tank charging is carried out even when standby operating mode is set
- There is a danger of scalding at target hot water temperatures over 60 c this is possible as the utility company evu is entitled to control current draw optimised according to supply and demand in the definitions for smart grid
- Smart grid sg
- Set 1 15 60 16
- Install scald protection in the hot water distri
- Ehs emergency operation
- Due to such forced charging the target hot water temperature in the hot water storage tank can exceed 60 c
- Bution line e g vta32 15 60 15 screw
- Activating deactivating emergency automatic operation
- X operation
- Way switching valves reference travel
- Special functions
- Manual operation
- 3 way switching valves reference travel
- X operation
- Special system settings
- Prior to initial commissioning of the floor heating system set the maximum temper ature limit in the rocon mb controller parameter t vbh1 max and the maximum permissible system temperature parameter max t flow
- In the event of malfunction or during manual operation the floor heating the screed or the floor structure could be damaged due to over heating
- If the floor heating is also used for room cooling the connection notes in the above point also apply to the connection of a moisture protection switch in the building
- Heat slope
- Expert
- Connect an overheating protection switch in the building at the ext plug connection to external operating mode switch over so that the rotex hpsu monobloc compact is switched to standby or summer operating mode see chap 3 with parameter room thermostat on or parameter interlink fct on the overheating protection switch must be connected so that the room thermostat s switching contact is interrupted
- Caution risk of overheating of floor heating
- Access rights technician code
- X operation
- Prior to initial commissioning and activation of cooling mode set the minimum temper ature limit to the minimum permissible system temperature in the rocon mb controller parameter min t flow cooling
- Manually adjusting the heat slope
- In the event of malfunction or incorrect parame ter settings the floor heating the screed or the floor structure could be damaged due to con densation
- Cooling slope
- Caution risk of condensation
- X operation
- With connected mixer module
- Weather dependent t hs control
- Frost protection function
- X operation
- Unsuitable feed temperatures can cause dam age to the floor heating system or dew formation on cooling surfaces
- Limit target feed temperatures to suitable temperature ranges
- Interlink function
- Design heat distribution areas with different design temperatures as hydraulically separate heating circuits if necessary design heating circuits with lim ited target feed temperatures as mixer cir cuits and regulate with a mixer module
- Caution
- Additional alternative heat generator
- X operation
- Special function switching contacts
- Heating support
- Air purge
- Anti legionella system
- X operation
- Warning
- There is a danger of scalding at target hot water temperatures over 60 c this is possible when using solar energy if the legionella protection or smart grid functions are activated or the target hot water temperature is set higher than 60 c
- Set 1 15 60 16
- Resetting to factory settings reset
- Option 2
- Option 1
- Install scald protection in the hot water distri
- Bution line e g vta32 15 60 15 screw
- X operation
- Screed program
- Option 3
- Function heating
- X operation
- Setting and starting the screed program
- Screed curing heating
- X operation
- Settings for optional circulation pump
- Relay test
- Defining the switching time program for the circulation pump
- X operation
- Remote control via internet
- X initial start up
- Initial start up
- Fundamental aspects of the ids and authorisations in the rocon system
- X initial start up
- Operating support during 1st commissioning and during system extensions
- For the rocon u1 room station
- For all rocon b1 and rocon u1 control units
- Mixer module rocon m1
- Commissioning rotex hpsu monobloc compact
- Assigning the terminal id on the rocon b1 control panel of the rotex hpsu monobloc compact
- X initial start up
- Putting optional rocon system components into operation
- X initial start up
- Sequence for initial commissioning see also chap 4
- Rocon u1 room station
- B configuration for mixing valve setting
- A configuration for the living room setting
- X initial start up
- Master rocon function
- Caretaker function
- Allocating the rocon m1 mixing module to a heat generator
- Allocating the rocon m1 mixing module to
- A heat generator
- Parameter overview
- For first commissioning or resetting to factory settings
- During initial commissioning after resetting to factory settings
- X parameter overview
- X parameter overview
- Rotary switch setting configuration
- Fa rotex rocon mb 09 2017 37
- After first commissioning after successful basic configuration
- Rotary switch setting remote param
- Rotary switch setting operating mode
- Rotary switch setting info
- Rotary switch setting dhw set temp
- Rotary switch setting dhw install
- Parameter levels for the rocon m1 mixer module
- Parameter levels for the rocon m1 mixer
- No function
- Module
- Fa rotex rocon mb 09 2017
- Exit key special function
- X parameter overview
- See chap 5
- Rotary switch setting time program
- Rotary switch setting set temp night
- Rotary switch setting set temp day
- X parameter overview
- Tab 5 12 parameters in the configuration rotary switch setting
- See chap 5
- Rotary switch setting time program
- Rotary switch setting remote param
- Rotary switch setting configuration
- Fa rotex rocon mb 09 2017 39
- Setup level
- Rotary switch setting configuration
- Parameter settings
- Explanation of the parameter tables
- X parameter settings
- X parameter settings
- Fa rotex rocon mb 09 2017 41
- X parameter settings
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 1 parameters in the configuration rotary switch setting setup level
- Fa rotex rocon mb 09 2017 43
- X parameter settings
- System configuration level
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 2 parameters in the configuration rotary switch setting system configuration level
- Hc configuration level
- Fa rotex rocon mb 09 2017 45
- Depending on the version individual information pa rameters are displayed that are not described in tab 6 2 for this see tab 6 12
- X parameter settings
- Fa rotex rocon mb 09 2017
- X parameter settings
- Rotary switch setting dhw install
- Fa rotex rocon mb 09 2017 47
- Dhw configuration level
- X parameter settings
- Tab 6 9 parameters in the dhw set temp rotary switch setting
- Tab 6 8 parameters in the set temp night rotary switch setting
- Tab 6 7 parameters in the set temp day rotary switch setting
- Tab 6 6 parameters in the operating mode rotary switch setting
- Rotary switch setting set temp night
- Rotary switch setting set temp day
- Rotary switch setting operating mode
- Rotary switch setting dhw set temp
- Fa rotex rocon mb 09 2017
- X parameter settings
- Tab 6 11 parameters in the remote param rotary switch setting
- Tab 6 10 parameters in the time program rotary switch setting
- Rotary switch setting time program
- Rotary switch setting remote param
- Rotary switch setting info
- Fa rotex rocon mb 09 2017 49
- X parameter settings
- To enter press the exit button for at least 5 s
- Tab 6 13 parameters at the special level level
- Tab 6 12 parameters in the info rotary switch setting
- Fa rotex rocon mb 09 2017
- Exit key special function
- See chap 6
- Basic configuration parameter level
- Rotary switch setting time program
- An unlimited scope of available parameters exists at the indi vidual levels
- Rotary switch setting set temp night
- After the system config parameter has been set to inactive or delete in the configuration rotary switch setting
- Rotary switch setting set temp day
- Rotary switch setting remote param
- Rotary switch setting operating mode
- Rotary switch setting info
- Rotary switch setting dhw set temp
- Rotary switch setting dhw install
- Rotary switch setting configuration
- Parameter levels of the rocon m1 mixer module
- X parameter settings
- Only the corresponding sections are referred to below signif icant differences are explained in more detail
- This parameter level only appears during initial commissioning if the answer selected for the use standard config prompt was no or
- On setting a rocon u1 room station assigned to the mixer module via the heating circuit id to living room the parameter t room adj is available the target room temperature can be changed in the range 5 k to 5 k with the rotary button this function is not available if the rocon u1 is used as a remote control in terminal function
- The parameter levels parameter meanings setting ranges and connected functions are basically described in the same way as in the previous sections
- On setting a control panel to mix valve x terminal function the displayed values refer to the components pump mix valve connected to the rocon m1 of the mixer circuit assigned via the device id
- Setup level
- No function
- See chap 6 3 and 6 3
- See chap 6 0
- Fa rotex rocon mb 09 2017 51
- X parameter settings
- Tab 6 15 parameters in the configuration rotary switch setting setup level
- Rotary switch setting configuration setup level
- Fa rotex rocon mb 09 2017
- X parameter settings
- Rotary switch setting configuration mixer config level
- Fa rotex rocon mb 09 2017 53
- X parameter settings
- Tab 6 16 parameters in the configuration rotary switch setting mixer config level
- Fa rotex rocon mb 09 2017
- X errors malfunctions and messages
- Troubleshooting
- Secure potential equalisation before touching electronic parts e g by touching an earthed metallic part
- Recognising errors correcting malfunctions
- Reading out the protocol
- Errors malfunctions and messages
- Electrostatic charges can lead to voltage arcing that can destroy the electronic components
- Current error display
- Caution
- X errors malfunctions and messages
- Malfunctions and fault codes
- Emergency operation
- Ehs emergency operation
- X glossary
- Glossary
- Switching time program
- X notes
- User specific settings
- X notes
- Rocon device id comments
- Parameters
- Ids in the rocon can bus system
- Fa rotex rocon mb 09 2017 59
- Enter the parameter changes you have made in the following table and in the rotex hpsu monobloc compact operating manual
- Circulation time
- Other items
- X list of keywords
- List of keywords
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Узнайте, как правильно настроить параметры системы для электрического обогрева и горячего водоснабжения. Оптимизируйте работу вашего оборудования для достижения максимальной эффективности.