4 Start-up
Installation and operating manual
16
EKHW(D/C/P)(300/500)(P)B
Daikin Altherma ST (Hot water storage tank)
008.1633099_00 – 06/2020
 3‒4 Filling the buffer storage tank(1)
a Hot water storage tank
b Drain-back solar – flow connection
c Safety overflow connection
d Drain-back solar – return flow connection
All EKHWD hot water storage tanks:
1 Mount the KFE filling connection (accessory KFE BA) to the
filling and draining connection on the EKHWD (" 3‒4 Filling
the buffer storage tank(1)"[416], itemd).
2 Connect the filling hose with backflow prevention (1/2") to the
previously installed KFE filling connection.
3 Fill the storage tank on the EKHWD until water comes out of the
safety overflow (" 3‒4 Filling the buffer storage
tank(1)"[416], itemc).
EKHWC/EKHWP hot water storage tank with solar system:
1 Install KFE filling connection (accessory KFE BA)
(a) With solar system: on the filling and draining connection
of the EKHWC/EKHWP.
(b) With solar system: on the connection bracket of the
control and pump unit (EKSRPS4A).
2 Connect the filling hose with backflow prevention (1/2") to the
previously installed KFE filling connection.
3 Only with solar system: Adjust the valve insert X1 on the
connecting angle so that the path to the filling hose is opened
("  3‒5 Filling the buffer storage tank(2)"[416]).
4 Open the valve on the KFE filling connection and the cold water
inlet and fill the storage tank on the EKHWC/EKHWP until water
comes out of the safety overflow (" 3‒5 Filling the buffer
storage tank(2)"[416]).
 3‒5 Filling the buffer storage tank(2)
4 Start-up
WARNING
Units which have been set-up and installed incorrectly
can be a health and safety risk endangering human life
and may not operate properly.
Installation commissioning may only be carried out by
authorised and trained heating technicians following
the provided installation and maintenance manual.
Only original replacement parts may be used.
CAUTION
A hot water storage tank commissioned improperly can
lead to property damage.
Observe the regulations in VDI 2035 in order to avoid
corrosion and deposits.
If the filling and top-up water has a high degree of
hardness, measures must be taken to stabilise this
hardness or soften the water.
Set the pressure reducer on the cold water connection
to a maximum of 6bar.
CAUTION
If the electric immersion heater is started with the storage
tank empty or not completely full, it can lead to a reduction
in performance of the electric heating (tripping of the safety
temperature limiter).
Operate the electric immersion heater only with the
storage tank completely full.
Incorrect start-up makes the manufacturer's guarantee for the unit
void. If you have questions, please contact our Technical Customer
Service.
Check all the points on the enclosed checklist. Make a record of
the test results and sign it, together with the operator.
If an electric immersion heater is fitted, set the desired storage
tank water temperature.