Outdoor Units • R410A • RZQ-B
Split Sky Air • Outdoor Units
8
2
3
3 Electrical data
3D048638A
RZQ71-125-140B7
Unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit Hz-volts
Voltage range
MCA TOCA MFA MSC RLA kW FLA kW FLA
SYMBOLS
MCA : Min. Circuit Amps (A)
TOCA : Total Over Current Amps (A)
MFA : Max. Fuse Amps (See note 7) (A)
MSC : MSC means the max. current
during the starting of compressor.
(A)
RLA : Rated Load Amps (A)
OFM : Outdoor Fan Motor (A)
IFM : Indoor Fan Motor
FLA : Full Load Amps
kW : Fan Motor Rated Output (kW)
NOTES
1 RLA is based on the following conditions:
Power supply: 50Hz 230V
Cooling
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 35°CDB
2 TOCA means the total value of each OC set
3 Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
4 Maximum allowable voltage unbalance between phases is 2%
5 MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
6 Select wire size based on the larger value of MCA or TOCA
7 MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
8 For more details concerning conditional connections, see http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the requested product type’’ and ’’English’’ from the drop
down lists, click the search button. Finally, click on the document title of your choice.
Heating
Indoor temperature 20.0°CDB
Outdoor temperature 7.0°CDB/6.0°CWB